9 cables, Cables, Dc-bus operation – Lenze 9400 Manual User Manual
Page 334
DC-bus operation
Basic dimensioning
Cables
8
334
EDS94SPP101 EN 7.1
With different motor cable lengths, per axis at least 25 % of the longest cable must be
considered when calculating the total motor cable length.
Example: 1
Motor cable length l
mot
[m]
Axis
Actual
value
min. 25 % of the longest cable
To be considered
1
6
0.25 * 20 = 5
6
2 ... 4
3 * 10
3 * 10
5
20
Õ
20
Total
56
max. permissible for 5 axes: ∑< 60
56
EMC class C2 will be complied with.
;
Example: 2
Motor cable length l
mot
[m]
Axis
Actual
value
min. 25 % of the longest cable
To be considered
1 ... 4
4 * 5
0.25 * 40 = 10
4 * 10
5
40
Õ
20
Total
60
max. permissible for 5 axes: ∑< 60
80
EMC class C2 will not be complied with.
:
Example: 3
Motor cable length l
mot
[m]
Axis
Actual
value
min. 25 % of the longest cable
To be considered
1 ... 3
3 * 100 Õ
0.25 * 100 = 25
3 * 100
4
50
50
5 ... 10
6 * 15
6 * 25
Total
410
max. permissible for 10 axes: ∑ < 500
500
EMC class C2 will be complied with.
;
Example: 4
Motor cable length l
mot
[m]
Axis
Actual
value
min. 25 % of the longest cable
To be considered
1 ... 4
4 * 100 Õ
0.25 * 100 = 25
4 * 100
5 ... 10
6 * 15
6 * 25
Total
490
max. permissible for 10 axes: ∑ < 500
550
EMC class C2 will not be complied with.
:
8.5.9
Cables
Select the cable cross-sections for the currents resulting from power P
DC100%
. Please
observe the standards and regulations applicable for the particular location and
application.