Regenerative power supply modules
Rated data (devices for 400/500V mains)
Mains filters for regenerative power supply modules
7
279
EDS94SPP101-7.1
7.3.7
Mains filters for regenerative power supply modules
When using the mains filters assigned, conditions must be observed for compliance with
EMC class C2:
ƒ
The measures for the use on IT systems must be applied to all axis modules in the
interconnection (separation of internal filter components from PE, ( 331)).
ƒ
The maximum sum total of all motor cable lengths (Σ l
mot
) for the filter used must
be observed.
Motor cable lengths in the interconnection
The assigned filters are designed for Σ l
mot
(E94AZMR...SDB: 60 m (= 6 x 10 m), E94AZMR...LDB: 500 m (= 10 x 50 m)).
For a different number of axis modules, Σ l
mot
can be determined from the following
diagrams.
25
30
35
40
45
50
55
60
65
70
2
4
6
8
10
12
14
16
18
20
Σl
[m]
n
SSP94FF015 B
Fig. 7-5
Filter E94AZMR...SDB (short distance): Sum total of motor cable lengths as a function of the number
of axis modules
6
8
10
12
14
16
18
20
n
250
300
350
400
450
500
550
600
650
700
Σl
[m]
SSP94FF015 A
Fig. 7-6
Filter E94AZMR...LDB (long distance): Sum total of motor cable lengths as a function of the number
of axis modules