Regenerative power supply modules, General data and operating conditions – Lenze 9400 Manual User Manual
Page 264
Regenerative power supply modules
General data and operating conditions
7
264
EDS94SPP101-7.1
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertical
Mounting clearances
Above/below
≥
80 mm / ≥ 120 mm
Observe the device-related
notes on mounting.
To the sides
Side-by-side mounting without
any clearance
Supply conditions for the regenerative power supply module
AC mains operation
Connection at the assigned mains filter
DC-bus operation
Direct connection of the axis modules via terminals or
busbar systems
See the chapter on DC-bus operation in the Hardware
Manual for further information.
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1
1K3 (-25 ... +60 °C)
Transport
IEC/EN 60721-3-2
2K3 (-25 ... +70 °C)
Operation
IEC/EN 60721-3-3
3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C:
Device size 1 ... 7: 2.5 %/°C
Device size 8S ... 10: 1 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution
EN 61800-5-1
Degree of pollution 2
Vibration resistance
(9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721-3-2
2M2
EN 61800-2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd
5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g