Single-axis controllers – Lenze 9400 Manual User Manual
Page 46
Single-axis controllers
General data and operating conditions
4
46
EDS94SPP101 EN 7.1
The available protective insulation within the controller of the ” 9400 Servo Drives” series
in accordance with EN 61800-5-1 is implemented with a rated voltage for the external
conductor/star point of up to 300 V for mains with neutral earthing.
The following graphic representation
ƒ
shows the arrangement of the terminal strips and the separate potential areas of
the controller.
ƒ
serves to determine the relevant protective insulation between two terminals in
differently insulated separate potential areas.
Reinforced insulation
Basic insulation
Functional insulation
Protective insulation acc. to
EN 61800-5-1
(Definition of terms: see glossary)
Ext. DC
I/O
X4
X6
X6
X5
X7
X7
X8
X8
X3
X2
X1
X105
X105
X106
X100
X107
MXI1
MXI2
Bus
Ext. DC
MSI
MMI
E94YCXX007zl
Terminal strip
Terminal
Terminal strip
Terminal
X100
z
L1, L2, L3
(only single drive)
z
+UG, -UG
X1
CAN on board 9400
X2
z
State bus
z
24 V (ext.)
X105
z
U, V, W
z
Rb1, Rb2
(only single drive)
X3
Analog input/output
X106
Motor PTC
X4
Digital outputs
X107
Control of motor holding
brake
X5
Digital inputs
X6
Diagnostics
X7
Resolver
X8
Encoder
MXI1, MXI2
Extension module
MMI
Memory module
MSI
Safety module
Example
Which type of protective insulation is used between the bus terminal of the device module
in slot MXI1 or MXI2 and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.
ƒ
The separate potential area of the device module bus terminal is ”functionally
insulated”.
ƒ
The separate potential area of the mains terminal has a ”reinforced insulation”.
Result: The insulation between the mains terminal X100 and the bus terminal is of the
”reinforced insulation” type.