Multi-axis controllers – Lenze 9400 Manual User Manual
Page 207
Multi-axis controllers
Control terminals
5
207
EDS94SPP101 EN 7.1
Digital inputs
The controller is provided with freely configurable digital inputs which can be used for
touch probe measurement (edge-controlled event).
The control input RFR for controller enable is firmly connected with the device control. It
must be wired to enable the controller with a HIGH signal.
Electrical data
24O
(external voltage source,
optional)
Rated voltage
24 V
According to IEC 61131-2
Current consumption
Max. 50 mA
RFR
DI1
...
DI8
Switching level
According to IEC 61131-2
LOW
0 V ... +5 V
HIGH
+15 V ... +30 V
Input current
Max. 8 mA
Note!
Digital inputs and digital outputs have separated reference potentials (GI and
GO). If you interconnect inputs and outputs, the reference potentials are
connected as well by an external bridge.
GND
Out
0
1
DI8
DI...
DI2
DI1
RFR
GI
X5
DI8
DI...
DI2
DI1
RFR
GI
X5
DO4
DO3
DO2
DO1
24O
GO
X4
SSP94X5DI1
Fig. 5-17
Wiring principle
Wiring of an external digital signal, e.g. a PLC
Wiring with a slave drive
X4
Terminal for the digital outputs
X5
Terminal for the digital inputs
Out
digital output signal, e.g. of a control
GND
Earth reference potential