Accessories (overview)
Safety modules
SM301
9
414
EDS94SPP101 EN 7.1
Technical data
The module and the safe output must be supplied with 24 V from safely separated power
supply units. To maintain electrical isolations, separate voltage supplies are required.
Detailed features of the 24-V supply
Terminal
Specification
[Unit]
min.
typ.
max.
+, -
Supply voltage of the module via a safely separated
power supply unit (SELV/PELV)
[V]
19.2
24
30
Input current
[mA]
350
24O, GO
Supply voltage of the safe output via a safely
separated power supply unit (SELV/PELV)
[V]
18
24
30
Input current
[mA]
1100
Functions
ƒ
Safe torque off (STO)
(formerly: Safe standstill, protection against unexpected start-up)
ƒ
Safe stop 1 (SS1)
ƒ
Safe stop 2 (SS2) - see SOS
ƒ
Safe stop emergency (SSE)
ƒ
Safe operational stop (SOS) - in accordance with EN 61800-5-2: SOS is designed with
speed monitoring
ƒ
Safe maximum speed (SMS)
ƒ
Safely limited speed 1 (SLS1)
ƒ
Safe operation mode selector (OMS)
ƒ
Safe enable switch (ES)
ƒ
Safe speed monitor (SSM)
ƒ
Safe monitor (output)
ƒ
Connection of safety sensors
ƒ
Safe parameterisation
ƒ
Safety bus connection (PROFIsafe V1)
Additional functions from SM301 V1.1
ƒ
Safely limited speed 2 (SLS2)
ƒ
Safely limited speed 3 (SLS3)
ƒ
Safely limited speed 4 (SLS4)
ƒ
Safe cascading (CAS) via SD-In4/SD-Out1
ƒ
Safety bus connection (PROFIsafe V2)