Multi-axis controllers, Rated data overview, Output data – Lenze 9400 Manual User Manual
Page 164
Multi-axis controllers
Rated data
Overview
5
164
EDS94SPP101 EN 7.1
Output data
Voltage
Frequency
1)
Current [A]
Number of
phases
Type
[V]
[Hz]
max. +45 °C
c
max. +55 °C
c
E94AMxE0024
0 - 230/400/500
0 - 599
1.5/1.5/1.3
1.1/1.1/1.0
3
E94AMxE0034
0 - 230/400/500
0 - 599
2.5/2.5/2.2
1.9/1.9/1.7
3
E94AMxE0044
0 - 230/400/500
0 - 599
4/4/3.5
3/3/2.6
3
E94AMxE0074
0 - 230/400/500
0 - 599
7/7/6.1
5.3/5.3/4.6
3
E94AMxE0094
0 - 230/400/500
0 - 599
9.3/9.3/8.2
7.0/7.0/6.2
3
E94AMxE0134
0 - 230/400/500
0 - 599
13/13/11.4
9.8/9.8/8.6
3
E94AMxE0174
0 - 230/400/500
0 - 599
16.5/16.5/14.4
12.4/12.4/10.8
3
E94AMxE0244
0 - 230/400/500
0 - 599
23.5/23.5/20.6
17.6/17.6/15.5
3
E94AMxE0324
0 - 230/400/500
0 - 599
32.0/32.0/25.9
24.0/24.0/19.4
3
c
Temperature in the control cabinet
1)
The limitation to 599 Hz does not apply to the ”servo control” modes (see C00006 = 1 or 2). Generally applies: the
output frequency is limited to 1/8 of the selected chopper frequency (see C00018).
Power loss P
V
[W]
Type
U
Lr
= 230 V
U
Lr
= 400 V
U
Lr
= 500 V
when controller is inhibited
E94AMxE0024
65
80
95
40
E94AMxE0034
75
95
110
E94AMxE0044
90
120
130
E94AMxE0074
105
145
170
E94AMxE0094
130
170
205
E94AMxE0134
160
215
255
E94AMxE0174
185
255
300
E94AMxE0244
235
320
385
E94AMxE0324
290
405
490