Regenerative power supply modules
Wiring
Wiring of control connections
7
301
EDS94SPP101-7.1
Tip!
Parameter setting and configuration can be carried out using the
L-force »Engineer«. For this purpose the Online Help and the Software Manual
for the standard device will guide you.
System bus CAN on board
Terminal X1
Labelling
Description
Pin 2
CAN-LOW
Pin 3
CAN-GND
Pin 7
CAN-HIGH
9400SSP000X1
(Housing)
CAN-Shield
24 V supply
Terminal X323
Labelling
Description
GE
GND external supply
SSP9400X11
24E
24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131-2, 22.8 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: max. 4 A for 100 ms
Terminal data
Conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
Terminal X2
Labelling
Description
GE
GND external supply
24E
24 V external supply via a safely separated power supply unit
(SELV/PELV)
9400SSP000X2
SB
State bus in/out (reference GE)
Terminal data
Conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule