Power supply modules, Internal brake chopper data – Lenze 9400 Manual User Manual
Page 222
Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
6
222
EDS94SPP101 EN 7.1
Output current and output power
100 %
5-s cycle
3-min cycle
Type
I
DC
[A]
P
DC
[kW]
I
DC
[A]
P
DC
[kW]
I
DC
[A]
P
DC
[kW]
E94APNE0104
10
3.6
40
14.4
15
5.4
E94APNE0104
+ E94AZMP0084
10
4.9
40
19.6
15
7.4
E94APNE0364
36
13.0
108
39.0
54
19.5
E94APNE0364
+ E94AZMP0294
36
17.5
108
52.5
54
26.3
E94APNE1004
100
36.2
200
109
150
54.3
E94APNE1004
+ E94AZMP0824
100
48.6
200
146
150
72.9
E94APNE2454
245
88.6
368
266
368
133
E94APNE2454
+ E94AZMP2004
245
119
368
357
368
179
100 %
Permanent rated values
5-s cycle
Cycle for the second-range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)
3-min cycle
Cycle for the minute-range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)
Internal brake chopper data
R
Bmin
[Ω]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E94APNE0104
27.0
26.9
19.5
9.7
2.6
4.3
0.5
0.5
E94APNE0364
12.0
60.4
43.8
27.0
8.7
3.0
0.5
0.5
E94APNE1004
5.0
145
105
58.2
17.0
3.6
0.5
0.5
E94APNE2454
2.8
259
188
104
30.3
3.6
0.5
0.5
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS - important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
- t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time