3 - 7

IP

N 07

4-

54

5-

P1

E

Cygnus 2 Operating Manual

Operate Display Description

1 Rate

2 Thickness

3 Power Level

4 State of Material

5 State Timer

6 Material Timer

7 Material Being Deposited

8 Source Number In Use

9 Sensor Number In Use

10 Crystal Position In Use

11 Graphical Display of Rate Deviation or Power

12 Date and Time

13 Message Area

14 Function Key Definitions

15 Crucible Position

16 State preceding Stop

During the OPERATE display, the function keys below the screen function as
explained in

Table 3-1

.

Table 3-1 Operate display function keys

Key Function

Description

F1

ZERO
THICKNESS

Pressing F1 resets the displayed thickness of the current
Material to zero.

F2

TOGGLE
MANUAL

Press F2 to put the Material in manual control so that the
power level is controlled by the Handheld Controller
(

section 3.5.5

). When in Manual, press F2 again to remove

the Material from the Manual state and place it into the
DEPOSIT state.

F3

SHOW ALL
MATERIALS/
SHOW GRAPH

Press F3 to toggle between showing all Materials (if more
are running) or showing only one Material