Echelon OpenLNS User Manual
Page 969
OpenLNS Programmer's Reference
932
The OpenLNS Server was able to
communicate with the device using
subnet/node addressing, but could not
communicate with the device using Neuron
ID addressing. However, through the use of
subnet/node addressed messages, the
OpenLNS Server has verified that the
device contains the expected Neuron ID.
This might be caused by intermittent device
or channel failures. You may want to retry
this method to see if the error persists.
4 lcaTestResultCommSnode
The OpenLNS Server was able to
communicate with the device using Neuron
ID addressing, but could not communicate
with the device using subnet/node
addressing. The OpenLNS Server was
unable to verify whether the device has
been configured with the proper
domain/subnet/node address. The device
may have reconfigured itself, the device
may have been reconfigured by another
network management tool, or the device
may be faulty. The device may be restored
using the Commission method.
5 lcaTestResultSnodeVerified
The OpenLNS Server was able to
communicate with the device using Neuron
ID addressing, but could not communicate
with the device using subnet/node
addressing. However, through the use of
Neuron ID addressed messages, The
OpenLNS Server has verified that the
device contains the expected subnet/node
address. This error can occur if the target
device is in an unconfigured state. The
device may need to be recomissioned or it
may be in the middle of a two-phase move.
It also might be caused by intermittent
device or channel failures. You may want to
retry this method to see if the error persists.
6 lcaTestResultDuplicateSnode
The OpenLNS Server was able to
communicate with the device using Neuron
ID addressing. However, when using
subnet/node addressing, the responding
device contains a different Neuron ID. This
failure indicates that multiple devices are
configured with the same
domain/subnet/node address. This could be