OpenLNS Programmer's Reference

932

The OpenLNS Server was able to

communicate with the device using

subnet/node addressing, but could not

communicate with the device using Neuron

ID addressing. However, through the use of

subnet/node addressed messages, the

OpenLNS Server has verified that the

device contains the expected Neuron ID.

This might be caused by intermittent device

or channel failures. You may want to retry

this method to see if the error persists.
4 lcaTestResultCommSnode
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. The OpenLNS Server was

unable to verify whether the device has

been configured with the proper

domain/subnet/node address. The device

may have reconfigured itself, the device

may have been reconfigured by another

network management tool, or the device

may be faulty. The device may be restored

using the Commission method.
5 lcaTestResultSnodeVerified
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing, but could not communicate

with the device using subnet/node

addressing. However, through the use of

Neuron ID addressed messages, The

OpenLNS Server has verified that the

device contains the expected subnet/node

address. This error can occur if the target

device is in an unconfigured state. The

device may need to be recomissioned or it

may be in the middle of a two-phase move.

It also might be caused by intermittent

device or channel failures. You may want to

retry this method to see if the error persists.
6 lcaTestResultDuplicateSnode
The OpenLNS Server was able to

communicate with the device using Neuron

ID addressing. However, when using

subnet/node addressing, the responding

device contains a different Neuron ID. This

failure indicates that multiple devices are

configured with the same

domain/subnet/node address. This could be