Mobileclasspinginterval, Mobileclspinginterval – Echelon OpenLNS User Manual
Page 792
OpenLNS Programmer's Reference
755
following value is defined for the
PingInterval
object in the
ConstClassIds
constant:
69 lcaClassIdPingIntervals
object
The object to be acted on.
Data Type
Integer.
Read/Write
Read only.
Added to API
Depends on the object used to access the property. Generally,
this property exists for an object as soon as the object is
added to the API.
MobileClassPingInterval
Summary
The cycle time (in seconds) for pinging devices that may
move. This value will be used for all devices and routers that
have their PingClass property set to lcaPingClassMobile.
All uninstalled devices are in this category because they are
more likely to be removed by the user without informing the
network management tool.
Availability
Local, full, and lightweight clients.
Syntax
permPing = piObject.MobileClsPingInterval
Element
Description
mobilePing
The ping interval (in seconds) for the
mobile ping class.
This value must be at least 30
seconds, and may not exceed any
non-zero value for the stationary
class. In addition, the following must
be true (excluding 0 values, which
means pinging is disabled):
MobileClsPingInterval <=
TemporaryClsPingInterval <=
StationaryClsPingInterval <=
PermanentClsPingInterval
You must change each of these
properties individually; therefore,
when you start a transaction, you can
set each of these properties to 0, set
the properties to the desired values,
and then commit the transaction.
Set this property to 0 to disable
pinging.
The minimum value is 30 seconds.
65535 (-1) means "do not change."