AlarmNotifyDisabled
Summary
Indicates whether alarm notification is disabled on the
LonMarkObject, or whether alarm notification can be
disabled on the LonMarkObject.
This description of this property depends on whether it was
accessed through the Status or ReportMask properties of a
Status property. Indicates whether alarm notification on
the LonMarkObject is currently disabled. If this property
is True, alarm notification has been disabled.
•
ReportMask property. Indicates whether alarm
notification can be disabled on the LonMarkObject. If this
property is True, then alarm notification can be disabled.
If alarm notification on the LonMarkObject can be
disabled, you can disable it by writing to the
lcaLonMarkObjectRequestAlarmNotifyDisabled
(12) value to the Request property of the LonMarkObject.
Availability
Local, full, and lightweight clients.
Syntax
notifyDisabledFlag= statusObject.AlarmNotifyDisabled
Element
Description
notifyDisabledFlag A Boolean value indicating whether
alarm notification on the
LonMarkObject has been disabled, or
whether alarm notification on the
LonMarkObject can be disabled.
Status Property
TRUE. Alarm notification on the
LonMarkObject has been
disabled.
FALSE. Alarm notification has not
been disabled.
ReportMask Property
TRUE. Alarm notification on the
LonMarkObject can be
disabled.
FALSE. Alarm notification can not
be disabled.
statusObject
The ObjectStatus object to be acted