OpenLNS Programmer's Reference
188
acknowledgment messages.
Do not use this service type on
channels that support altnerate
frequencies because the message will
only be sent using the primary path.
See the AltPathType property for
more information.
3 lcaSvcRequest
Request/Response messaging service.
You can use this value when sending
explicit messages if the device
receiving the message is designed to
send a response message for the
specified message code.
object
acted on.
Data Type
Integer.
Read/Write
Read/write.
Added to API
Prior to LNS Release 3.0.
TransmitTimer
Summary
Specifies the interval between lcaSvcAckd and
lcaSvcRequest messages.
Availability
Local, full, and lightweight clients.
Syntax
transTimerValue = cdtObject.
Element
Description
cdtObject
acted on.
transTimerValue
The value of the transmit timer.
This property will only be read by the
Object Server if the
lcaConnPropsTansmitTimer (128)
option is set in the
ConnectDescTemplate object’s
PropertyOptions property. Otherwise,
the transmit timer used by the
connection will be calculated
automatically based on the network
topology and channel delays.
This property accepts a range of
encoded values from 0 to 15. The
encoded transmit timer values are as
follows:
Encoded Value Seconds
0