Echelon OpenLNS User Manual
Page 91
OpenLNS Programmer's Reference
54
2 lcaTestResultCommNeuronId
The OpenLNS Server was unable to
communicate with the device using Neuron
ID addressing. Because the device has not
been added or defined, the OpenLNS Server
could not test the device using subnet/node
ID addressing. The OpenLNS Server might
not be attached to the network, the Network
Service Device might be unconfigured, the
target device might not be attached to the
network, the target device may be powered
off, or the target device may be faulty.
3
lcaTestResultCommNeuronIdVerified
The OpenLNS Server was able to
communicate with the device using
subnet/node addressing, but could not
communicate with the device using Neuron
ID addressing. However, through the use of
subnet/node addressed messages, the
OpenLNS Server has verified that the device
contains the expected Neuron ID. This
might be caused by intermittent device or
channel failures. You may want to retry this
method to see if the error persists.
4 lcaTestResultCommSnode
The OpenLNS Server was able to
communicate with the device using Neuron
ID addressing, but could not communicate
with the device using subnet/node
addressing. The OpenLNS Server was
unable to verify whether the device has been
configured with the proper
domain/subnet/node address. The device
may have reconfigured itself, the device may
have been reconfigured by another network
management tool, or the device may be
faulty. The device may be restored using the
Commission method.
5 lcaTestResultSnodeVerified
The OpenLNS Server was able to
communicate with the device using Neuron
ID addressing, but could not communicate
with the device using subnet/node
addressing. However, through the use of
Neuron ID addressed messages, The
OpenLNS Server has verified that the device
contains the expected subnet/node address.
This error can occur if the target device is in
an unconfigured state. The device may need