Echelon OpenLNS User Manual
Page 1011
OpenLNS Programmer's Reference
974
lcaErrNsNotImplemented
16
The specified service or option is not implemented by the specified server. This error
could indicate a bad service parameter. This is an internal error and should be reported
to customer support.
lcaErrNsErrorInfo
17
The service failed. When you encounter this error, a service-specific error status is
available in the LastError property of the System
lcaErrNsServiceFailure
18
The requested service failed. This is an internal error, and should be reported to
customer support. This error may occur for a remote client operation when the OpenLNS
Server has shutdown.
lcaErrNsMsgRejectedByNode
19
A node returned a negative response to a command from NSS. This could be due to a
LonTalk authentication failure. It may also result from an inconsistency between the
program interface defined in the database and what the node actually supports.
lcaErrNsPrematureRelease
20
This is an internal error and should be reported to customer support.
lcaErrNsRootBusy
21
A transaction is still in progress. This is an internal error and should be reported to
customer support.
lcaErrNsRootDoesNotExist
22
The service depends on a transaction that does not exist. This is an internal error and
should be reported to customer support.
lcaErrNsNoFreeRootTransactions
23
This is an internal error and should be reported to customer support.
lcaErrNsCantFindObject
24
One of the objects needed to complete the service is not in the NSS's database.
lcaErrNsDuplicateObject
25
An attempt was made to add an object that already exists.
lcaErrNsCommError
26
The NSS cannot communicate with the node. This may be because the Neuron ID
referenced by the application is invalid or does not exist, the NSS or the node is not
physically attached to the media, the NSS is not configured (because the MgmtMode
property was not set to lcaMgmtModePropagateConfigUpdates after the database was
initially created), problems with the physical media, or the NSS timers (set using the
RetryCount and TxTimer properties of the System
lcaErrNsOperationError
27
The node failed to go online, offline or to reset when requested to do so. This may be due
to a problem in the implementation of the device.