Contact expansion module, Analog expansion module, Crank settings – Winco DGC-2020 User Manual
Page 95: Crank settings -25, Figure 4-21. remote module setup -25

Contact Expansion Module
A J1939 Address
C
must be entered when the optional CEM-2020 is enabled
D
. Select number of CEM-
2020 outputs
E
.
Analog Expansion Module
A J1939 Address
F
must be entered when the optional AEM-2020 is enabled
G
.
BESTCOMSPlus system settings (DGC-2020, System Parameters, Remote Module Setup) are illustrated
in Figure 4-21.
Figure 4-21. Remote Module Setup
A
LSM J1939 Address: Adjustable from 1 to 253 in increments of 1.
B
Load Share Module:
Enable or Disable.
C
CEM J1939 Address: Adjustable from 1 to 253 in increments of 1.
D
Contact Expansion Module: Enable or Disable.
E
CEM Outputs: 18 Outputs or 24 Outputs.
F
AEM J1939 Address: Adjustable from 1 to 253 in increments of 1.
G
Analog Expansion Module: Enable or Disable.
Crank Settings
The DGC-2020 can be programmed for either cycle or continuous engine cranking
A
. Cycle cranking
provides multiple engine starting attempts
B
. Each starting attempt consists of a fixed interval of engine
cranking
C
followed by a rest interval of the same duration. Continuous cranking
D
provides a single,
extended engine-starting attempt.
The DGC-2020 uses the engine speed signal (supplied by a magnetic pickup (MPU) or the generator
frequency) and the Crank Disconnect Limit setting
E
to detect engine startup (and determine when engine
cranking can be stopped). The Crank Disconnect Limit setting is expressed as a percentage of the
nominal engine speed.
If desired, cycle or continuous cranking can be delayed after initiating engine startup. During this delay
F
,
the Pre-Start output closes to energize the engine glow plugs or pre-start lubrication pump. The Pre-Start
output can be configured to open upon the conclusion of engine cranking or remain closed as long as the
engine is running
G
.
The Pre-Start can be configured
H
during the resting state. If Preheat Before Crank is selected, the Pre-
Start output will be closed for a time equal to the Pre-crank delay time prior to re-entering the cranking
state. If the Pre-crank delay setting is longer than the rest interval, the Pre-Start output will be closed for
the entire rest time.
Under normal operation, engine rpm is used to determine crank disconnect. The Oil Pressure Crank
Disconnect
I
provides a secondary indication that the engine is running so that the starter will be
disconnected even if no engine rpm sources are functioning. When enabled, oil pressure is used as a
check of whether the engine is running. If the engine oil pressure is above the threshold
J
, the starter will
be disconnected from the engine.
BESTCOMSPlus engine cranking settings (DGC-2020, System Parameters, Crank Settings) are
illustrated in Figure 4-22.
9400200990 Rev K
DGC-2020 BESTCOMSPlus Software
4-25