Virtual input 1 open, Virtual input 2 close, Virtual input 2 open – Winco DGC-2020 User Manual
Page 305: Virtual input 3 close, Virtual input 3 open, Virtual input 4 close, Virtual input 4 open, Estop latch status, Future use, Communication

9400200990 Rev K
DGC-2020 Modbus
Communication
B-29
Register Description Type
Units
Scaling
Factor
R/W
Range
43776
Virtual Input 1 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43778
Virtual Input 2 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43780
Virtual Input 2 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43782
Virtual Input 3 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43784
Virtual Input 3 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43786
Virtual Input 4 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43788
Virtual Input 4 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43790
ESTOP Latch Status
Int32
N/A
N/A
R
0 = Disabled
1 = Enabled
43792-4006 FUTURE USE
Communication
Register Description Type
Units
Scaling
Factor
R/W
Range
44008-48
RESERVED
44050
DHCP Enabled
Uint32
N/A
N/A
R
0 = Disabled
1 = Enabled
44052
Active IP Address
Uint32
N/A
N/A
R
0 - 4294967295
44054
Gateway IP Address
Uint32
N/A
N/A
R
0 - 4294967295
44056
Subnet Mask
Uint32
N/A
N/A
R
0 - 4294967295
44058-064
RESERVED
44066-248
FUTURE USE
Protection
Register Description Type
Units
Scaling
Factor
R/W Range
44250
3 Phase Overcurrent Pickup (51-
1)
Uint32 CentiAmp
Centi
RW
18 - 775
44252
3 Phase Overcurrent Time Dial
(51-1)
Uint32 DeciUnit
Deci
RW
0 - 300
44254
3 Phase Overcurrent Curve (51-
1)
Uint32 N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
44256
3 Phase Overcurrent Alarm
Configuration (51-1)
Uint32 N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
44258
1 Phase Overcurrent Pickup (51-
1)
Uint32 CentiAmp
Centi
RW
18 - 775
44260
1 Phase Overcurrent Time Dial
(51-1)
Uint32 DeciUnit
Deci
RW
0 - 300