Winco DGC-2020 User Manual
Page 87

9400200990 Rev K
DGC-2020 BESTCOMSPlus Software
4-17
secondary base speed is 1,800 rpm. The Accelerator Position setting
C
is expressed as a percentage and
tells the Volvo Penta ECU where to set the engine speed (trim) relative to the base speed. The range of
the setting is the base speed
120 rpm. A setting of 0% will cause the engine to run at 120 rpm below the
base speed, a setting of 50% will cause the engine to run at the base speed, and a setting of 100% will
cause the engine to run at 120 rpm above the base speed. The Accelerator Position setting is linear with
a gain of 2.4 rpm/percentage. This setting is not saved in nonvolatile memory and defaults back to 50%
after DGC-2020 operating power is cycled.
If the engine is configured as MTU MDEC, the configuration of the following settings is necessary:
MDEC Module Type
D
Speed Demand Switch
E
Engine
RPM
F
If the engine is configured as MTU ADEC, the configuration of the following settings is necessary:
Speed Demand Switch
E
- Specifies speed demand source for the MTU engine ECU.
Engine
RPM
F
- Requested engine RPM when speed demand source is analog CAN for an MTU ECU.
Overspeed
Test
G
- Temporarily drives an MTU ECU into overspeed for testing overspeed.
Governor Param Switch Over
H
- Specifies which governor parameters an MTU ECU should use.
Trip
Reset
I
- Resets trip information such as trip fuel used, trip hours, trip idle time, etc.
Int Oil Prime
J
- Causes an MTU ECU engine to perform an internal lubrication cycle.
If the engine is configured as MTU ECU7, the configuration of the following settings is necessary:
Speed Demand Switch
E
- Specifies speed demand source for the MTU engine ECU.
Engine
RPM
F
- Requested engine RPM when speed demand source is analog CAN for an MTU ECU.
Overspeed
Test
G
- Temporarily drives an MTU ECU into overspeed for testing overspeed.
Speed
Up
K
- Increases speed of the MTU ECU.
Speed
Down
L
- Decreases speed of the MTU ECU.
Speed Demand Limit
M
- Turns the speed demand limit on or off.
Increased
Idle
N
- Sets the MTU ECU idle.
Trip
Reset
I
- Resets trip information such as trip fuel used, trip hours, trip idle time, etc.
Int Oil Prime
J
- Causes an MTU ECU engine to perform an internal lubrication cycle.
Engine Start Prime
O
- Turns the engine start prime on or off.
Fan
Override
P
- Turns the fan override on or off.
Mode
Switch
Q
- Turns the mode switch on or off.
Governor Param Switch Over
H
- Specifies which governor parameters an MTU ECU should use.
Governor Param Set Select
R
- Sets the governor parameter set select.
CAN Rating Switch 1 & 2
S
- Turns the CAN rating switch 1 & 2 on or off.
Cylinder Cutout Disable 1 & 2
T
- Turns the cylinder cutout disable 1 & 2 on or off.
The Volvo Penta ECU configuration is applicable only to the EDC3 and EMS2 models of Volvo Penta
engine controllers.