Figure 4-50. Bus Condition Detection Settings

A

Dead Bus Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments.

B

Dead Bus Time Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.

C

Gen and Bus Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 1,200 Vac in 1 Vac

increments.

D

Gen and Bus Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 12,000 Vac in 1 Vac

increments.

E

Gen and Bus Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz

increments for 50/60 Hz generator frequency (style number x1xxxxxxx).

F

Gen and Bus Stable Underfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz

increments for 50/60 Hz generator frequency (style number x1xxxxxxx).

G

Bus Stable Activation Delay: Adjustable from 0.1 to 600 in 1 second increments.

H

Bus Failed Activation Delay: Adjustable from 0.1 to 600 in 1 second increments.

I

Low Line Scale Factor: Adjustable from 0 to 3 in increments of 0.001.

Automatic Synchronizer (Optional)
Two methods of generator synchronization are offered: phase lock loop and anticipatory

A

. In both

methods, the DGC-2020 adjusts the frequency and voltage of the generator to match that of the bus
(mains) and then connects the generator to the bus by closing the breaker. Anticipatory mode has the
added capability of compensating for the breaker closing time (the delay between when a breaker close
command is issued and the breaker blades close). The DGC-2020 calculates the advance phase angle