NOTES

1.) If the DGC-2020 is providing one end of the J1939 bus, a 120

 terminating

resistor should be installed across terminals 48 (CANL) and 49 (CANH).

2.) If the DGC-2020 is not part of the J1939 bus, the stub connecting the DGC-

2020 to the bus should not exceed 914 mm (3 ft) in length.

3.) The maximum bus length, not including stubs, is 40 m (131 ft).

4.) The J1939 drain (shield) should be grounded at one point only. If grounded

elsewhere, do not connect the drain to the DGC-2020.

AEM-2020

(Optional)

DGC-2020

Other

Devices

P0053-95

Engine

120 ohm

Termination

CAN-H

CAN-L

LSM-2020

(Optional)

CEM-2020

(Optional)

120 ohm

Termination

Bus

Stub

Figure 6-4. CANbus Interface with DGC-2020 providing One End of the Bus

DGC-2020

AEM-2020

(Optional)

Other

Devices

P0053-94

Engine

120 ohm

Termination

CAN-H

CAN-L

LSM-2020

(Optional)

CEM-2020

(Optional)

120 ohm

Termination

Bus

Stub

Figure 6-5. CANbus Interface with Optional AEM-2020 providing One End of the Bus

6-8

DGC-2020 Installation

9400200990 Rev K