beautypg.com

Winco DGC-2020 User Manual

Page 289

background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-13

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40287-97 RESERVED

40298

Read Relay Image of both Main
and Aux Output

individual bits
are 0 or 1

R

Main is in lower byte and Aux is in
upper byte.
b0 = Aux Output 1,
b1 = Aux Output 2,
b2 = Aux Output 3,
b3 = Aux Output 4,
b4 = Aux Output 5,
b5 = Aux Output 6,
b6 = Aux Output 7,
b7 = Aux Output 8.
b8 = Master Start Relay,
b9 = Fuel Solenoid Relay,
b10 = PreHeat PreLube Relay,
b11 = Alarm Relay,
b12 = UNASSIGNED,
b13 = Buzzer On,
b14 = EPS Loaded Relay,
b15 = PreAlarm Relay,

40299 RESERVED

J1939 DIAGNOSTIC TROUBLE CODES

40300

Active DTC Number 16 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40301

Active DTC Number 16 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40302

Active DTC Number 15 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40303

Active DTC Number 15 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40304

Active DTC Number 14 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40305

Active DTC Number 14 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40306

Active DTC Number 13 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40307

Active DTC Number 13 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40308

Active DTC Number 12 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40309

Active DTC Number 12 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40310

Active DTC Number 11 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40311

Active DTC Number 11 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40312

Active DTC Number 10 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40313

Active DTC Number 10 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40314

Active DTC Number 9 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40315

Active DTC Number 9 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40316

Active DTC Number 8 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40317

Active DTC Number 8 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40318

Active DTC Number 7 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40319

Active DTC Number 7 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40320

Active DTC Number 6 – Lower
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73

40321

Active DTC Number 6 – Upper
Two Bytes

0-65535 R

Half of a set of DTC data as defined in

SAE J1939-73