Table 10-3. CANbus Interface Terminals

Terminal Description

P1- HI (CAN H)

CAN high connection (yellow wire)

P1- LO (CAN L)

CAN low connection (green wire)

P1-

(SHIELD)

CAN drain connection

NOTES

1. If the AEM-2020 is providing one end of the J1939 bus, a 120

 terminating

resistor should be installed across terminals P1- LO (CANL) and P1- HI
(CANH).

2. If the AEM-2020 is not part of the J1939 bus, the stub connecting the AEM-

2020 to the bus should not exceed 914 mm (3 ft) in length.

3. The maximum bus length, not including stubs, is 40 m (131 ft).

4. The J1939 drain (shield) should be grounded at one point only. If grounded

elsewhere, do not connect the drain to the AEM-2020.

DGC-2020

AEM-2020

Other

Devices

P0053-62

Engine

120 ohm

Termination

CAN-H

CAN-L

LSM-2020

(Optional)

CEM-2020

(Optional)

120 ohm

Termination

Bus

Stub

Figure 10-5. CANbus Interface with AEM-2020 providing One End of the Bus

9400200990 Rev K

DGC-2020 AEM-2020 (Analog Expansion Module)

10-7