Remote outputs status bits, Cem alarm bits, Remote configurable inputs pre-alarm bits – Winco DGC-2020 User Manual
Page 317: Remote configurable inputs alarm bits, Aem alarm bits, Reserved, Generator frequency, Bus frequency, Power factor, Ecu lamp status

9400200990 Rev K
DGC-2020 Modbus
Communication
B-41
Register Description Type
Units
Scaling
Factor
R/W Range
44966
Remote Outputs Status
Bits
Int32
N/A
N/A
R
Bit 0 = Remote Output 13
Bit 1 = Remote Output 14
Bit 2 = Remote Output 15
Bit 3 = Remote Output 16
Bit 4 = Remote Output 17
Bit 5 = Remote Output 18
Bit 6 = Remote Output 19
Bit 7 = Remote Output 20
Bit 8 = Remote Output 21
Bit 9 = Remote Output 22
Bit 10 = Remote Output 23
Bit 11 = Remote Output 24
Bit 12 = Remote Output 25
Bit 13 = Remote Output 26
Bit 14 = Remote Output 27
Bit 15 = Remote Output 28
Bit 16 = Remote Output 29
Bit 17 = Remote Output 30
Bit 18 = Remote Output 31
Bit 19 = Remote Output 32
Bit 20 = Remote Output 33
Bit 21 = Remote Output 34
Bit 22 = Remote Output 35
Bit 23 = Remote Output 36
44968
CEM Alarm Bits
Uint32 N/A
N/A
R
Bit 0 = CEM Comm Fail
Bit 1 = Duplicate CEM
Bit 2 = CEM Hardware Mismatch
44970
Remote Configurable
Inputs Pre-Alarm Bits
Uint32 N/A
N/A
R
Bit 0 = Remote Input 17
Bit 1 = Remote Input 18
Bit 2 = Remote Input 19
Bit 3 = Remote Input 20
Bit 4 = Remote Input 21
Bit 5 = Remote Input 22
Bit 6 = Remote Input 23
Bit 7 = Remote Input 24
Bit 8 = Remote Input 25
Bit 9 = Remote Input 26
44972
Remote Configurable
Inputs Alarm Bits
Uint32 N/A
N/A
R
Bit 0 = Remote Input 17
Bit 1 = Remote Input 18
Bit 2 = Remote Input 19
Bit 3 = Remote Input 20
Bit 4 = Remote Input 21
Bit 5 = Remote Input 22
Bit 6 = Remote Input 23
Bit 7 = Remote Input 24
Bit 8 = Remote Input 25
Bit 9 = Remote Input 26
44974
AEM Alarm Bits
Uint32 N/A
N/A
R
Bit 0 = AEM Comm Fail
Bit 1 = Duplicate AEM
44976-84
RESERVED
44986
Generator Frequency
Int32
N/A
Deci
R
0 - 4400
44988
Bus Frequency
Int32
N/A
Deci
R
0 - 440
44990
Power Factor
Int32
N/A
Centi
R
(-100) - 100
44992-99
RESERVED
45000
ECU Lamp Status
Int32
N/A
N/A
R
Bit 24 = Malfunction
Bit 27 = Stop
Bit 28 = Warning
Bit 31 = Protect
45002
Number of DTC’s
Int32
N/A
N/A
R
(-32768) - 32767
45004-490
RESERVED
45500
Analog Input 1 Metering
Value
Int32 DeciUnit
Deci R (-99990)
-
99990
45502
Analog Input 2 Metering
Value
Int32 DeciUnit
Deci R (-99990)
-
99990