Overspeed alarm enable, Overspeed alarm threshold, Overspeed alarm activation delay – Winco DGC-2020 User Manual
Page 310: Low fuel level alarm enable, Low fuel level alarm threshold, Low fuel level alarm activation delay, High coolant temp pre-alarm enable, High coolant temp pre-alarm threshold, Metric high coolant temp pre-alarm threshold, Low coolant temp pre-alarm enable

B-34 DGC-2020
Modbus
Communication
9400200990 Rev K
Register Description Type
Units
Scaling
Factor
R/W
Range
44516
Overspeed Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44518
Overspeed Alarm Threshold
Uint32 Percent
N/A
RW
105 - 140
44520
Overspeed Alarm Activation
Delay
Uint32 Millisecond Milli
RW 0
-
500
44522
Low Fuel Level Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44524
Low Fuel Level Alarm Threshold
Uint32 Percent
N/A
RW
0 - 100
44526
Low Fuel Level Alarm Activation
Delay
Int32
Second
N/A
RW
0 - 30
44528
High Coolant Temp Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44530
High Coolant Temp Pre-Alarm
Threshold
Uint32 Deg F
N/A
RW
100 - 280
44532
Metric High Coolant Temp Pre-
Alarm Threshold
Int32
Deg C
N/A
RW
38 - 138
44534
Low Coolant Temp Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44536
Low Coolant Temp Pre-Alarm
Threshold
Uint32 Deg F
N/A
RW
35 - 150
44538
Metric Low Coolant Temp Pre-
Alarm Threshold
Int32
Deg C
N/A
RW
2 - 66
44540
High Fuel Level Pre-Alarm
Threshold
Int32
Percent
N/A
RW
0 - 100
44542
High Fuel Level Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44544
High Fuel Level Pre-Alarm
Activation Delay
Int32
Second
N/A
RW
0 - 30
44546
Low Fuel Level Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44548
Low Fuel Level Pre-Alarm
Threshold
Uint32 Percent
N/A
RW
10 - 100
44550
Low Battery Pre-Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44552
Low Battery Pre-Alarm
Threshold
Uint32 DeciVolt
Deci
RW
60 - 240
44554
Low Battery Pre-Alarm
Activation Delay
Uint32 Second
N/A
RW
1 - 10
44556
Weak Battery Pre-Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44558
Weak Battery Pre-Alarm
Threshold
Uint32 DeciVolt
Deci
RW
40 - 160
44560
Weak Battery Pre-Alarm
Activation Delay
Uint32 Second
N/A
RW
1 - 10
44562
Battery Overvoltage Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44564
Low Oil Press. Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44566
Low Oil Press. Pre-Alarm
Threshold
Uint32 PSI
N/A
RW
3 - 150
44568
Metric Low Oil Press. Pre-Alarm
Threshold
Int32
Kpa
N/A
RW
21 - 1034
44570
Engine Overload 1 Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44572
Engine Overload 1 Pre-Alarm
Threshold
Int32
Percent
N/A
RW
95 - 140
44574
ECU Comms Fail Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44576
Active DTC Pre-Alarm Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable