Alarm metering, Pre-alarm metering, Mtu alarm metering – Winco DGC-2020 User Manual
Page 313: Mtu pre-alarm metering, Sender fail alarm metering, Protection alarm metering, Future use

9400200990 Rev K
DGC-2020 Modbus
Communication
B-37
Register Description Type
Units
Scaling
Factor
R/W Range
44812
Alarm Metering
Int32
N/A
N/A
R
Bit 0 = Overspeed
Bit 1 = Hi Coolant Temp
Bit 2 = Low Oil Pressure
Bit 3 = Low Fuel Level
Bit 4 = Global Sender Fail
Bit 5 = Loss of ECU Comms
Bit 6 = Overcrank
Bit 7 = Emergency Shutdown
Bit 8 = Loss of ECU Shutdown
Bit 9 = ECU Low Coolant Level
44814
Pre-Alarm Metering
Int32
N/A
N/A
R
Bit 0 = Hi Coolant Temp
Bit 1 = Low Oil Pressure
Bit 2 = Low Fuel Level
Bit 3 = Low Coolant Temp
Bit 4 = Low Battery Voltage
Bit 5 = Weak Battery
Bit 6 = Battery Overvoltage
Bit 7 = Maintenance Due
Bit 8 = Loss of ECU Comms
Bit 9 = Diagnostic Trouble Code
Bit 10 = Engine kW Overload
Bit 11 = Loss of Rem. Mod. Com
Bit 12 = High Fuel Level
Bit 13 = Sync Fail at Gen Brkr
Bit 14 = Gen Brkr Fail to Close
Bit 15 = Gen Brkr Fail to Open
Bit 16 = Sync Fail at Mains Brkr
Bit 17 = Mains Brkr Fail to Close
Bit 18 = Mains Brkr Fail to Open
44816
MTU Alarm Metering
Int32
N/A
N/A
R
Bit 0 = High Charge Air Temp
Bit 1 = High Oil Temp
Bit 2 = High Coolant Temp
Bit 3 = Low Aftrcooler Cool. Level
Bit 4 = Low Fuel Delivery Press.
Bit 5 = Low Oil Pressure
Bit 6 = Overspeed
Bit 7 = Combined Red
44818
MTU Pre-Alarm Metering
Int32
N/A
N/A
R
Bit 0 = High ECU Temp.
Bit 1 = High Oil Temp.
Bit 2 = High Intercooler Temp.
Bit 3 = High Charge Air Temp.
Bit 4 = High Coolant Temp.
Bit 5 = Shutdown Override
Bit 6 = High Fuel Rail Press.
Bit 7 = Low Fuel Rail Press.
Bit 8 = Low Coolant Level
Bit 9 = Low Charge Air Press.
Bit 10 = Low Fuel Delivery Press.
Bit 11 = Low Oil Press.
Bit 12 = Combined Yellow
44820
Sender Fail Alarm
Metering
Int32
N/A
N/A
R
Bit 0 = Speed
Bit 1 = Oil Pressure
Bit 2 = Coolant Temp
Bit 3 = Fuel Level
Bit 4 = Generator Voltage
44822
Protection Alarm Metering Int32
N/A
N/A
R
Bit 0 = 51-1 Overcurrent
Bit 1 = 47 Phase Imbalance
Bit 2 = 27-1 Undervoltage
Bit 3 = 59-1 Overvoltage
Bit 4 = 81 Overfrequency
Bit 5 = 81 Underfrequency
Bit 6 = 51-2 Overcurrent
Bit 7 = 27-2 Undervoltage
Bit 8 = 59-2 Overvoltage
Bit 9 = 32 Reverse Power
Bit 10 = 40Q Loss of Excitation
44824-26
FUTURE USE