Cumulative number of engine starts, Session start date month, Session start date day – Winco DGC-2020 User Manual
Page 315: Session start date year, Generator status, 8 = connecting state, Future use, Reserved, Global alarm, Global pre-alarm

9400200990 Rev K
DGC-2020 Modbus
Communication
B-39
Register Description Type
Units
Scaling
Factor
R/W Range
44858
Session Total Engine Run
Hrs.
Int32
Hour
N/A
R
0 - 99999
44860
Session Total Engine Run
Min.
Int32
N/A
N/A
R
0 - 59
44862
Session Loaded Engine
Run Hrs.
Int32
Hour
N/A
R
0 - 99999
44864
Session Loaded Engine
Run Min.
Int32
N/A
N/A
R
0 - 59
44866
Session Unloaded Engine
Run Hrs.
Int32
Hour
N/A
R
0 - 99999
44868
Session Unloaded Engine
Run Min.
Int32
N/A
N/A
R
0 - 59
44870
Session kW-Hrs
Int32
KiloWattHour
N/A
R
0 - 999999999
44872
Cumulative Number of
Engine Starts
Uint32 N/A
N/A
RW
0 - 65535
44874
Session Start Date Month
Uint32 N/A
N/A
RW
1 - 12
44876
Session Start Date Day
Uint32 N/A
N/A
RW
1 - 31
44878
Session Start Date Year
Uint32 N/A
N/A
RW
0 - 99
44880
Generator Status
Uint32 N/A
N/A
R
0 = RESET State
1 = READY State
2 = CRANKING State
3 = RESTING State
4 = RUNNING State
5 = ALARM State
6 = PRESTART State
7 = COOLING State
8 = CONNECTING State
9 = DISCONNECT State
10 = PULSING State
11 = UNLOADING State
44882-918
FUTURE USE
44920-48
RESERVED
44950
Global Alarm
Uint32 N/A
N/A
R
0 = No system alarms in effect
1 = System alarm(s) in effect
44952
Global Pre-Alarm
Uint32 N/A
N/A
R
0 = No system pre-alarms in effect
1 = System pre-alarm(s) in effect
44954
Local Configurable Inputs
Pre-Alarm Bits
Int32
N/A
N/A
R
Bit 0 = Input 1
Bit 1 = Input 2
Bit 2 = Input 3
Bit 3 = Input 4
Bit 4 = Input 5
Bit 5 = Input 6
Bit 6 = Input 7
Bit 7 = Input 8
Bit 8 = Input 9
Bit 9 = Input 10
Bit 10 = Input 11
Bit 11 = Input 12
Bit 12 = Input 13
Bit 13 = Input 14
Bit 14 = Input 15
Bit 15 = Input 16