Page 130: Multigen management -60, Avr output -60, Governor output -60, Figure 4-54. avr output settings -60

P
Derivative Filter Constant (Td): Adjustable from 0 to 1 in increments of 0.001.
Q
Loop Gain (Kg): Adjustable from 1 to 1,000 in increments of 0.001.
R
Droop Percentage: Adjustable from 0 to 10 percent in 0.001 % increments.
S
Speed Droop Gain: Adjustable from 0 to 1,000 in increments of 0.001.
T
Ramp Rate: Adjustable from 0 to 100 percent/second in 0.1 %/s increments.
U
Base Load Level Source: User Setting, LSM Analog Input 1, or Analog Inputs 1-8.
V
Base Load Level: Adjustable from 0 to 100 percent in 1 % increments.
W
Baseload Analog Max: Adjustable from 0 to 100 percent in 0.1 % increments.
X
Baseload Analog Min: Adjustable from 0 to 100 percent in 0.1% increments.
Y
Breaker Open Setpoint: Adjustable from 0 to 1,000 in increments of 1.
MULTIGEN MANAGEMENT
This group of settings is used when an optional LSM-2020 (Load Share Module) is connected to the
DGC-2020. Multigen management settings consist of settings for AVR output, governor output, load
share output, demand start/stop, generator sequencing, and network configuration.
AVR Output
The AVR output
A
of the LSM-2020 is used to change the voltage setpoint of the generator. If the
response
B
is set for increasing, an increased bias will cause higher voltage. If the response
B
is set for
decreasing, an increased bias will cause lower voltage. Settings are provided for minimum output
current
C
, maximum output current
D
, minimum output voltage
E
, and maximum output voltage
F
.
BESTCOMSPlus AVR output settings (DGC-2020, Multigen Management, AVR Output) are illustrated in
Figure 4-54.
Figure 4-54. AVR Output Settings
A
Output Type: Voltage or Current.
B
Response: Increasing or Decreasing.
C
Min Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
D
Max Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
E
Min Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments.
F
Max Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments.
Governor Output
The governor output
A
of the LSM-2020 is used to change the speed setpoint of the generator. If the
response
B
is set for increasing, an increased bias will cause faster speed. If the response
B
is set for
decreasing, an increased bias will cause slower speed. Settings are provided for minimum output
current
C
, maximum output current
D
, minimum output voltage
E
, and maximum output voltage
F
.
BESTCOMSPlus governor output settings (DGC-2020, Multigen Management, Governor Output) are
illustrated in Figure 4-55.
4-60
DGC-2020 BESTCOMSPlus Software
9400200990 Rev K