Pulse outputs, Bus condition detection – Winco DGC-2020 User Manual
Page 300

B-24 DGC-2020
Modbus
Communication
9400200990 Rev K
Register Description
Type
Units
Scaling
Factor
R/W
Range
42328
kw Integrator Limit Plus
Float
N/A
N/A
RW
0 - 1000
42330
kw Integrator Limit Minus
Float
N/A
N/A
RW
(-1000) - 0
42332
kw Output Upper Limit
Float
N/A
N/A
RW
0 - 1000
42334
kw Output Lower Limit
Float
N/A
N/A
RW
(-1000) - 0
42336 RESERVED
42338
Droop Percent
Float
Percent
N/A
RW
0 - 10
42340
Load Control
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42342
kw Load Rate
Int32
N/A
Deci
RW
0 - 1000
42344
Breaker Open Setpoint
Int32
N/A
Deci
RW
0 - 1000
42346
AVR Bias Control Output Type
Int32
N/A
N/A
RW
0 = Contact
1 = Analog
42348
Governor Bias Control Output Type
Int32
N/A
N/A
RW
0 = Contact
1 = Analog
42350
Speed Droop Gain
Float
N/A
N/A
RW
0 - 1000
42352
Voltage Droop Gain
Float
N/A
N/A
RW
0 - 1000
42354
Speed Trim Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42356
Voltage Trim Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42358
Ramped Watt Demand Per Unit
Float
N/A
N/A
R
0 - 100
42360
Watt Demand Per Unit
Float
N/A
N/A
R
0 - 100
42362
Speed PID Output
Float
N/A
N/A
R
0 - 100
42364
kw PID Output
Float
N/A
N/A
R
0 - 100
42366
Volt PID Output
Float
N/A
N/A
R
0 - 100
42368
Speed Trim Setpoint
Int32
DeciHertz
Deci
RW
470 - 4400
42370-498 FUTURE
USE
Pulse Outputs
Register Description
Type
Units
Scaling
Factor
R/W
Range
42500
AVR Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42502
AVR Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42504
AVR Bias Contact Type
Int32
N/A
N/A
RW
0 = Continuous
1 = Proportional
42506 RESERVED
42508
Governor Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42510
Governor Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42512
Governor Bias Contact Type
Int32
Decisecond
Deci
RW
0 = Continuous
1 = Proportional
42514 RESERVED
42516-748 FUTURE
USE
Bus Condition Detection
Register Description
Type
Units
Scaling
Factor
R/W
Range
42750
Gen Sensing Dead Bus Pickup
Int32
Volt
N/A
RW
0 - 4800
42752
Gen Sensing Dead Bus Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42754 RESERVED
42756
Gen Sensing Stable Undervoltage Pickup
Int32
Volt
N/A
RW
10 - 99999
42758
Gen Sensing Stable Undervoltage Dropout
Int32
Volt
N/A
RW
10 - 99999
42760
Gen Sensing Stable Overvoltage
Int32
Volt
N/A
RW
10 - 99999
42762
Gen Sensing Stable Overvoltage Dropout
Int32
Volt
N/A
RW
10 - 99999
42764
Gen Sensing Stable Underfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42766
Gen Sensing Stable Underfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400