Name Description
Symbol
Status Input
Auto Restart
TRUE when the Automatic Restart function is active.
Status Input
Battery Charger Fail
TRUE when the Battery Charger Fail input is TRUE.
Status Input
Battle Override
TRUE when the Battle Override input is TRUE.
Status Input
Bus Dead
TRUE when the Bus Dead condition settings have
been exceeded.
Status Input
Bus Fail
TRUE when the Bus Fail condition settings have
been exceeded.
Status Input
Bus Stable
TRUE when the Bus Stable condition settings have
been exceeded.
Status Input
Configurable
Elements 1-8
TRUE when the Configurable Element x logic output
is TRUE.
Status Input
Configurable
Protection 1-8
TRUE when the Configurable Protection x Over
Threshold #1 is TRUE.
Status Input
Configurable
Protection 1-8
TRUE when the Configurable Protection x Over
Threshold #2 is TRUE.
Status Input
Configurable
Protection 1-8
TRUE when the Configurable Protection x Under
Threshold #1 is TRUE.
Status Input
Configurable
Protection 1-8
TRUE when the Configurable Protection x Under
Threshold #2 is TRUE.
Status Input
Contact Expansion
Module
Contact Expansion Module Connected. TRUE when
an optional CEM-2020 is connected to the DGC-
2020.
Status Input
Cool Down Timer
Active
TRUE when the Cool Down Timer is timing out.
Status Input
Emergency Stop
TRUE when the Emergency Stop button has been
pressed.
Status Input
Engine Running
TRUE while the Engine is Running.
Status Input
EPS Supplying
Load
TRUE while the EPS is supplying load.
Status Input
Front Panel Buttons
TRUE while the AUTO front panel button is pressed.
Status Input
Front Panel Buttons
TRUE while the DOWN front panel button is
pressed.
9400200990 Rev K
DGC-2020 BESTlogic+ Programmabl
5-3
e Logic