Overvoltage (59-1, 59-2), Figure 4-41. undervoltage protection settings -45 – Winco DGC-2020 User Manual
Page 115

The hysteresis setting
D
functions as an undervoltage dropout by preventing rapid switching of the pickup
output.
A frequency-based inhibit setting
E
prevents a 27 trip from occurring during an undervoltage condition
associated with system startup.
A low-line scale factor setting
F
is used to automatically adjust the undervoltage pickup settings in
applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the protection settings. The value of the scale factor setting serves as a multiplier for the pickup
settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor
setting is 2.000, the pickup setting will be doubled (2.000
PU).
The element is disabled when Alarm Configuration is set to “None”. Element status is available in
BESTlogic+ Programmable Logic when “Status Only” is selected.
BESTCOMSPlus voltage protection settings (DGC-2020, Generator Protection, Voltage, Undervoltage)
are illustrated in Figure 4-41. The 27-1 element is shown.
Figure 4-41. Undervoltage Protection Settings
A
Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.
B
Activation Delay:
Adjustable from 0 to 30 s in 0.1 s increments.
C
Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.
D
Hysteresis: Adjustable from 1 to 60 Vac in 1 Vac increments.
E
Inhibit Frequency: Adjustable from 20 to 400 Hz in 1 Hz increments.
F
Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.
Overvoltage (59-1, 59-2)
Two sets of overvoltage settings are provided for each element: one for three-phase generator
connections and one for single-phase generator connections. The pickup setting entered is based on the
VT secondary side (DGC-2020). When a single-phase override contact input is received, the DGC-2020
automatically switches from the three-phase overvoltage settings to the single-phase overvoltage
settings.
An overvoltage condition is annunciated when the average of the three-phase (three-phase mode) or the
line-to-line voltage (single-phase mode) increases above the corresponding 59 pickup setting
A
for the
duration of the corresponding 59 activation delay
B
. An overvoltage annunciation can be user-selected to
trigger a pre-alarm
C
(warning) or alarm
C
(shutdown). An overvoltage annunciation can also be user-
configured to close a programmable output.
The hysteresis setting
D
functions as an undervoltage dropout by preventing rapid switching of the pickup
output.
A low-line scale factor setting
E
is used to automatically adjust the overvoltage pickup settings in
applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the protection settings. The value of the scale factor setting serves as a multiplier for the pickup
9400200990 Rev K
DGC-2020 BESTCOMSPlus Software
4-45