beautypg.com

Winco DGC-2020 User Manual

Page 258

background image

A-4

DGC-2020 Time Overcurrent Characteristic Curves

9400200990 Rev K















Table A-3 .Time Dial Setting Cross-Reference

Electromechanical Relay Time Dial Setting

0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

11.0

Curve

Equivalent

To

Basler Electric Equivalent Time Dial Setting

S, S1

ABB

CO-2 0.3 0.8 1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7

L, L1

ABB

CO-5 0.4 0.8 1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9

D

ABB

CO-6 0.5 1.1 2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1

M

ABB

CO-7 0.4 0.8 1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8

I, I1

ABB

CO-8 0.3 0.7 1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0

V, V1

ABB

CO-9 0.3 0.7 1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6

E, E1

ABB

CO-11 0.3 0.7 1.5 2.4 3.2 4.2 5.0 5.7 6.6 7.8 8.5 10.3

I2

GE

IAC-51 0.6 1.0 1.9 2.7 3.7 4.8 5.7 6.8 8.0 9.3 10.6 N/A

V2

GE

IAC-53 0.4 0.8 1.6 2.4 3.4 4.3 5.1 6.3 7.2 8.4 9.6 N/A

S2

GE

IAC-55 0.2 1.0 2.0 3.1 4.0 4.9 6.1 7.2 8.1 8.9 9.8 N/A

L2

GE

IAC-66 0.4 0.9 1.8 2.7 3.9 4.9 6.3 7.2 8.5 9.7 10.9 N/A

E2

GE

IAC-77 0.5 1.0 1.9 2.7 3.5 4.3 5.2 6.2 7.4 8.2 9.9 N/A