9400200990 Rev K
DGC-2020 Human-Machine Interface
2-3
Permissions
If communications access is active through the modem or USB, the front panel will display REMOTE
COMMS, FRONT PANEL IS READ ONLY and the summary screen. This informs the user that the front
panel can only be used for viewing metering data and settings information. Remote access must be
ended before modifying settings through the front panel.
Summary Screen and Configurable Metering
The summary screen can be set to standard or scrolling. When set to standard, only the following are
displayed:
VOLT
AMP
PH
Hz
OIL
FUEL
TEMP
BATT
When set to standard, individual phase information can be automatically toggled at a rate set by the
Phase Toggle Delay setting. Navigate to the SETTINGS, GENERAL SETTINGS, FRONT PANEL HMI
screen and edit PH TOG DELAY. When the Phase Toggle Delay is set to zero, information for each
phase is obtained by pressing the Up or Down arrow keys on the front panel HMI. When it is set to a
number other than zero, the display will toggle through the phases automatically at the rate specified by
the Phase Toggle Delay Setting.
When the summary screen is set to scrolling, you can select/configure the metering values that are
displayed. Up to 20 values can be displayed and these values will scroll at a delay time specified by the
user. To select a standard or scrolling summary, navigate to the SETTINGS, GENERAL SETTINGS,
FRONT PANEL HMI screen and edit the SUMMARY VIEW. The SCROLL DELAY setting is also found on
this screen.
To select the scrolling values, navigate to the SETTINGS, GENERAL SETTINGS, FRONT PANEL HMI
screen and edit the CONFIGURABLE METERING. The following items may be selected by the user to be
placed in the scrolling summary:
NONE (Removes a line from the scrolling list)
BLANK (Shows nothing on this line)
OIL
P
TEMP
BATT
V
RPM
RPM
SRC
FUEL
RUN
HRS
GEN
VAB
GEN
VBC
GEN
VCA
GEN
VAN
GEN
VBN
GEN
VCN
BUS
Hz
BUS
V
GEN
Hz
GEN
PF
KWH
GEN
IA
GEN
IB
GEN
IC
KW
A
KW
B
KW
C
KW
TOT
KVA
A
KVA
B
KVA
C
KVA
TOT
ALG_IN_X (X = 1 to 8) (with AEM-2020)
RTD_IN_X (X = 1 to 8) (with AEM-2020)
THRM_CPL_X (X = 1 to 2) (with AEM-2020)
Sleep Mode
Sleep mode serves as a power saving feature. If the DGC-2020 is in Off mode or Auto mode not running
and a key is not pressed for more than 15 minutes, the front panel LCD backlight and LCD heater are
turned off. The DGC-2020 resumes normal display operation when any front panel button is pressed or
the genset is started remotely via the ATS input. The DGC-2020 will not go to sleep while in an Alarm
state. If needed, Sleep mode can be permanently disabled via BESTCOMSPlus or the front panel.