Components, Components -10 – Winco DGC-2020 User Manual
Page 172

Name Description
Symbol
Senders
Coolant Temp
Sender Fail
TRUE when the Coolant Temp Sender Fail is
configured as either a Pre-Alarm or Alarm and the
activation delay has expired.
Fuel Level Sender
Fail
TRUE when the Fuel Level Sender Fail is
configured as either a Pre-Alarm or Alarm and the
activation delay has expired.
Oil Pressure
Sender Fail
TRUE when the Oil Pressure Sender Fail is
configured as either a Pre-Alarm or Alarm and the
activation delay has expired.
Speed Sender Fail
TRUE when the Speed Sender Fail activation delay
has expired.
Voltage Sensing
Fail
TRUE when the Voltage Sensing Fail is configured
as either a Pre-Alarm or Alarm and the activation
delay has expired.
Logic Control Relays
Inputs
Input 1-16
Additional logic inputs. TRUE when the associated
Logic Control Relay Output is TRUE.
Outputs
Output 1-16
Additional logic outputs.
Components
This group contains Logic Gates, Pickup and Dropout Timers, Latches, and Comment Blocks. Table 5-2
lists the names and descriptions of the objects in the Components group.
Table 5-2. Components Group, Names and Descriptions
Name Description
Symbol
Logic Gates
AND
Input Output
5-10
DGC-2020 BESTlogic+ Programmable Logic
9400200990 Rev K
0 0
0
0 1
0
1 0
0
1 1
1
NAND
Input Output
0 0
1
0 1
1
1 0
1
1 1
0
OR
Input Output
0 0
0
0 1
1
1 0
1
1 1
1
NOR
Input Output
0 0
1
0 1
0
1 0
0
1 1
0