Maintenance interval pre-alarm enable, Maintenance interval pre-alarm threshold, Speed sender fail activation delay – Winco DGC-2020 User Manual
Page 311: Ecu low coolant level alarm enable, Ecu low coolant level alarm threshold, Ecu low coolant level pre-alarm enable, Ecu low coolant level pre-alarm threshold, Battery overvoltage alarm threshold, Engine overload 1 pre-alarm, 3 phase hysteresis

9400200990 Rev K
DGC-2020 Modbus
Communication
B-35
Register Description Type
Units
Scaling
Factor
R/W
Range
44578
Maintenance Interval Pre-Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44580
Maintenance Interval Pre-Alarm
Threshold
Uint32 Hour
N/A
RW
0 - 5000
44582
Speed Sender Fail Activation
Delay
Int32
Second
N/A
RW
0 - 300
44584
ECU Low Coolant Level Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44586
ECU Low Coolant Level Alarm
Threshold
Uint32 Percent
N/A
RW
1 - 99
44588
ECU Low Coolant Level Pre-
Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44590
ECU Low Coolant Level Pre-
Alarm Threshold
Uint32 Percent
N/A
RW
1 - 99
44592
Battery Overvoltage Alarm
Threshold
Int32
DeciVolt
Deci
RW
120 - 320
44594
Engine Overload 1 Pre-Alarm
3 Phase Hysteresis
Int32
DeciVolt
Deci
RW
1 - 10
44596
Engine Overload 1 Pre-Alarm
1 Phase Threshold
Int32
Percent
N/A
RW
95 - 140
44598
Engine Overload 1 Pre-Alarm
1 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44600
Engine Overload 1 Pre-Alarm
1 Phase Low Line Scale Factor
Float
N/A
N/A
RW
0 - 3
44602
Engine Overload 2 Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44604
Engine Overload 2 Pre-Alarm
3 Phase Threshold
Int32
Percent
N/A
RW
95 - 140
44606
Engine Overload 2 Pre-Alarm
3 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44608
Engine Overload 2 Pre-Alarm
1 Phase Threshold
Int32
Percent
N/A
RW
95 - 140
44610
Engine Overload 2 Pre-Alarm
1 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44612
Engine Overload 2 Pre-Alarm
1 Phase Low Line Scale Factor
Float
N/A
N/A
RW
0 - 3
44614
Engine Overload 3 Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44616
Engine Overload 3 Pre-Alarm
3 Phase Threshold
Int32
Percent
N/A
RW
95 - 140
44618
Engine Overload 3 Pre-Alarm
3 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44620
Engine Overload 3 Pre-Alarm
1 Phase Threshold
Int32
Percent
N/A
RW
95 - 140
44622
Engine Overload 3 Pre-Alarm
1 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44624
Engine Overload 3 Pre-Alarm
1 Phase Low Line Scale Factor
Float
N/A
N/A
RW
0 - 3
44626
LSM Comm Failure Pre-alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44628
Intergenset Comm Failure Pre-
alarm Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44630
AVR Bias Output Limit Pre-
alarm Activation Delay
Int32
Second
N/A
RW
1 - 15
44632
AVR Bias Output Limit Pre-
alarm Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable