Modem setup (optional), Modem setup (optional) -18, Figure 4-17. ecu setup -18 – Winco DGC-2020 User Manual
Page 88

Figure 4-17. ECU Setup
A
ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, or MTU ECU7.
B
Speed Select: Primary or Secondary.
C
Accelerator Position: Adjustable from 0 to 100% in 1% increments.
D
MDEC Module Type: CAN Module 201, 302, 303, or 304.
E
Speed Demand Switch: Analog CAN, Up Down ECU, Up Down CAN, Analog ECU, Frequency, No
CAN Demand.
F
Engine RPM: Adjustable from 1,400 to 2,000 in increments of 1.
G
Overspeed Test: Off or On.
H
Governor Param Switch Over: Off or On.
I
Trip Reset: Press to set.
J
Int Oil Prime: Press to set.
K
Speed Up: Press to set.
L
Speed Down: Press to set.
M
Speed Demand Limit: Off or On.
N
Increased Idle: 0 to 1,000 in increments of 1.
O
Engine Start Prime: Off or On.
P
Fan Override: Off or On.
Q
Mode Switch: Off or On.
R
Governor Param Set Select: 0 to 1,000 in increments of 1.
S
CAN Rating Switch 1 & 2: Off or On.
T
Cylinder Cutout Disable 1 & 2: Off or On.
Modem Setup (Optional)
DGC-2020 controllers with style number xxxxxMxxx are equipped with an internal telephone modem that
has dial-in and dial-out capability. The modem gives the DGC-2020 the ability to dial up to four telephone
numbers
A
and annunciate user-selected conditions to specified pagers
B
. These user-selected conditions
include
C
:
27-1 Trip Alarm
27-2 Trip Alarm
32 Trip Alarm
40 Trip Alarm
47 Trip Alarm
51-1 Trip Alarm
51-2 Trip Alarm
51-3 Trip Alarm
59-1 Trip Alarm
59-2 Trip Alarm
4-18
DGC-2020 BESTCOMSPlus Software
9400200990 Rev K