beautypg.com

Generator sequencing, Communications, Canbus – Winco DGC-2020 User Manual

Page 224: Ethernet port, Bestcomsplus software, Lsm-2020 plugin for bestcomsplus, Device info, Generator sequencing -4, Communications -4, Canbus -4

background image

8-4

DGC-2020 LSM-2020 (Load Share Module)

9400200990 Rev K

Generator Sequencing

Machines can be added or removed from the power system based on load demand. The following criteria
should be considered before adding or removing a machine:

 Machine

Priority

 Engine Run Time

 Machine

Size

 kW% of the load/demand

 Out of Service machines

Communications

The LSM-2020 communication ports include CAN terminals and an Ethernet port.

CANbus

A Control Area Network (CAN) is a standard interface that enables communication between the LSM-
2020 and the DGC-2020.

Ethernet Port

An Ethernet port provides communications via BESTCOMSPlus to the LSM-2020 and to the DGC-2020
that the module is connected to. Ethernet communication between LSM-2020s allows for generator
sequencing on an islanded system. Firmware updates to the LSM-2020 are made through the Ethernet
port. Firmware updates to the DGC-2020 are only available through the USB port of the DGC-2020. Refer
to Section 4, BESTCOMSPlus, for information on configuring Ethernet communication and updating
firmware in the DGC-2020.

Industrial Ethernet devices designed to comply with IEC 61000-4 series of specifications are
recommended.

BESTCOMSPlus SOFTWARE

BESTCOMSPlus provides the user with a point-and-click means to set and monitor the LSM-2020.
Installation and operation of BESTCOMSPlus is described in Section 4, BESTCOMSPlus Software.

LSM-2020 Plugin for BESTCOMSPlus

The setup utility that installs BESTCOMSPlus on your PC also installs the LSM-2020 plug-in. Refer to
Section 4, BESTCOMSPlus Software, for information on activating the plugin.

The LSM-2020 plugin is used to set device security and view device information such as firmware version
and serial number.

LSM-2020 operational settings are found in the DGC-2020 plugin for BESTCOMSPlus. Refer to Section
4, BESTCOMSPlus Software, for a detailed description of each setting.

The LSM-2020 plugin has two screens: Device Info and Device Security Setup.

Device Info

Information about a LSM-2020 communicating with BESTCOMSPlus can be obtained on the Device Info
tab of BESTCOMSPlus.

Select application version

A

when configuring LSM-2020 settings off-line. When on-line, read-only

information includes application version

B

, boot code version

C

, application build

D

, serial number

E

,

application part number

F

, and model number

G

.

BESTCOMSPlus device information values and settings are illustrated in Figure 8-1.