Operating power, Aem-2020 inputs and outputs, Operating power -5 – Winco DGC-2020 User Manual
Page 249: Aem-2020 inputs and outputs -5, Figure 10-2. input and output terminals -5, Table 10-1. operating power terminals -5

is mounted permanently to the board. Connector screw terminals accept a maximum wire size of 12
AWG. Thermocouple connectors accept a maximum thermocouple wire diameter of 0.177 inches (4.5
mm). Maximum screw torque is 5 inch-pounds (0.56 N
m).
Operating Power
The Analog Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
polarity will not cause damage, the AEM-2020 will not operate. Operating power terminals are listed in
Table 10-1.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Analog Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.
Table 10-1. Operating Power Terminals
Terminal Description
P1-
(SHIELD)
Chassis ground connection
P1- – (BATT–)
Negative side of operating power input
P1- + (BATT+)
Positive side of operating power input
AEM-2020 Inputs and Outputs
Input and output terminals are shown in Figure 10-2 and listed in Table 10-2.
.
Figure 10-2. Input and Output Terminals
9400200990 Rev K
DGC-2020 AEM-2020 (Analog Expansion Module)
10-5