1.18 aac for 1a cts, 7.75 aac for 5a cts, 9.9 for 40607=0-15 (inverse) – Winco DGC-2020 User Manual
Page 296: 30.0s for 40607=16 (fixed), 15 for inverse, 16 for fixed, 0=none, 1=pre-alarm, 2=alarm, Volts ac, 30.0 seconds, Hertz, 55.0 hz for 50-hz config

B-20 DGC-2020
Modbus
Communication
9400200990 Rev K
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40509-604 RESERVED
OVERCURRENT
40605
51 Pick-up – 3-phase
18-118,
90-775
R W
0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs
40606
51 Time Dial – 3-phase
0-99,
0-300
R W
0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)
40607
51 Curve – 3-phase
0-16
R W
0-15 for inverse, 16 for fixed
40608
51 Alarm Config. – 3-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
40609
51 Pick-up – 1-phase
18-118,
90-775
R W
0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs
40610
51 Time Dial – 1-phase
0-99,
0-300
R W
0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)
40611
51 Curve – 1-phase
0-16
R W
0-15 for inverse, 16 for fixed
40612
51 Alarm Config. – 1-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
PHASE IMBALANCE
40613
47 Pick-up
5-100
R W
Volts AC
40614
47 Time Delay
0-300
R W
0.0-30.0 seconds
40615
47 Alarm Configuration
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
UNDERVOLTAGE
40616
27 Pick-up – 3-phase
70-576
R W
Volts AC
40617
27 Time Delay – 3-phase
0-300
R W
0.0-30.0 seconds
40618
27 Inhibit Frequency- 3-ph.
20-400
R W
Hertz
40619
27 Alarm Config. – 3-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
40620
27 Pick-up – 1-phase
70-576
R W
Volts AC
40621
27 Time Delay – 1-phase
0-300
R W
0.0-30.0 seconds
40622
27 Inhibit Frequency – 1-ph.
20-400
R W
Hertz
40623
27 Alarm Config. – 1-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
OVERVOLTAGE
40624
59 Pick-up – 3-phase
70-576
R W
Volts AC
40625
59 Time Delay – 3-phase
0-300
R W
0.0-30.0 seconds
40626
59 Alarm Config. – 3-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
40627
59 Pick-up – 1-phase
70-576
R W
Volts AC
40628
59 Time Delay – 1-phase
0-300
R W
0.0-30.0 seconds
40629
59 Alarm Config. – 1-phase
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
UNDERFREQUENCY
40630 81U
Pick-up
450-550,
550-650,
3600-4400
R W
45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit
40631
81U Time Delay
0-300
R W
0.0-30.0 seconds
40632
81U Inhibit Voltage
70-576
R W
Volts AC
40633
81U Alarm Configuration
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
OVERFREQUENCY
40634 81O
Pick-up
450-550,
550-650,
3600-4400
R W
45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit
40635
81O Time Delay
0-300
R W
0.0-30.0 seconds
40636
81O Alarm Configuration
0-2
R W
0=None, 1=Pre-Alarm, 2=Alarm
GENERATOR PROTECTION STATUS
40637
Gen Protection Status (upper 16
bits)
0-65535 R b16-b31 UNASSIGNED
40638
Gen Protection Status (lower 16
bits)
0-65535 R
b0 = overvoltage trip,
b1 = undervoltage trip,
b2 = overfrequency trip,
b3 = underfrequency trip,
b4 = overcurrent trip,
b5 = phase imbalance trip,
b6-b15 UNASSIGNED
40639
Gen Protection Pre-Alarms (upper
16 bits)
0-65535 R b16-b31 UNASSIGNED