Remote contact inputs, Remote analog inputs, Remote contact inputs -31 – Winco DGC-2020 User Manual
Page 101: Remote analog inputs -31, Figure 4-28. remote lsm inputssettings -31, Figure 4-29. remote contact inputs settings -31

Figure 4-28. Remote LSM InputsSettings
A
Input Type: Voltage or Current.
B
Min/Max Input Voltage: Adjustable from 0 to 10 volts in 0.1 V increments.
C
Min/Max Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
Remote Contact Inputs
An optional CEM-2020 (Contact Expansion Module) provides 10 contact inputs. Each of the 10 contact
inputs can be independently configured to annunciate an alarm or pre-alarm
A
when the input senses a
contact closure. A user-adjustable time delay
B
can be set to delay recognition of a contact input. By
default, all inputs are configured so that they do not trigger an alarm or pre-alarm.
To make identifying the contact inputs easier, a user-assigned name
C
can be given to each input.
Contacts can be recognized
D
always or only while the engine is running.
Remote contact input status is available in BESTlogic+ Programmable Logic when “None” is selected for
Alarm Configuration.
BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Inputs, Remote Contact
Inputs) are illustrated in Figure 4-29.
Figure 4-29. Remote Contact Inputs Settings
A
Alarm Configuration: None, Alarm, or Pre-Alarm.
B
Activation Delay: Adjustable from 0 to 300 s in 1 s increments.
C
Label Text: An alphanumeric character string with a maximum of 16 characters.
D
Contact Recognition: Always or While Engine Running Only.
Remote Analog Inputs
An optional AEM-2020 (Analog Expansion Module) provides eight analog inputs. To make identifying the
analog inputs easier, a user-assigned name
A
can be given to each input.
9400200990 Rev K
DGC-2020 BESTCOMSPlus Software
4-31