Pre-start contact config, System units, Battery volts – Winco DGC-2020 User Manual
Page 302: Off mode status, Run mode status, Auto mode status, Virtual input 1 status, Virtual input 2 status, Virtual input 3 status, Virtual input 4 status

B-26 DGC-2020
Modbus
Communication
9400200990 Rev K
Register Description Type
Units
Scaling
Factor
R/W Range
43502
Pre-Start Contact Config
Int32
N/A
N/A
RW
0 = Open After Disconnect
1 = Closed While Running
43504
System Units
Int32
N/A
N/A
RW
0 = English
1 = Metric
43506
Battery Volts
Int32
N/A
N/A
RW
0 = 12V
1 = 24V
43508
Off Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43510
Run Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43512
Auto Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43514
Virtual Input 1 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43516
Virtual Input 2 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43518
Virtual Input 3 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43520
Virtual Input 4 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43522
RTC Clock Hour
Int32
Hour
N/A
RW
0 - 23
43524
RTC Minute
Int32
Minute
N/A
RW
0 - 59
43526
RTC Second
Int32
Second
N/A
RW
0 - 59
43528
RTC Month
Int32
N/A
N/A
RW
1 - 12
43530
RTC Day
Int32
N/A
N/A
RW
1 - 31
43532
RTC Year
Int32
N/A
N/A
RW
0 - 99
43534
RTC DST Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43536
Gen PT Primary
Int32
Volt
N/A
RW
1 - 99999
43538
Gen PT Secondary
Int32
Volt
N/A
RW
1 - 480
43540
Gen CT Primary
Int32
Amp
N/A
RW
1 - 9999
43542
Bus PT Primary
Int32
Volt
N/A
RW
1 - 99999
43544
Bus PT Secondary
Int32
Volt
N/A
RW
1 - 480
43546
Cranking Style
Uint32
N/A
N/A
RW
0 = Continuous
1 = Cycle
43548
Number of Crank Cycles
Uint32
N/A
N/A
RW
1 - 7
43550
Cycle Crank Time
Unit32
Second
N/A
RW
5 - 15
43552
Continuous Crank Time
Unit32
Second
N/A
RW
5 - 60
43554
Crank Disconnect Limit
Uint32
Percent
N/A
RW
10 - 100
43556
Pre Crank Delay
Uint32
Second
N/A
RW
0 - 30
43558
Configured Gen Connection
Uint32
N/A
N/A
RW
0 = Delta
1 = Wye
2 = 1-phase AB
3 = 1-phase AC
4 = Grounded Delta
43560
Gen Rated Frequency
Int32
Hertz
N/A
RW
0 = 50 Hz
1 = 60 Hz
43562
Rated Kw
Uint32
KiloWatt
N/A
RW
5 - 9999
43564
Rated Engine RPM
Uint32
RPM
N/A
RW
750 - 3600
43566
No Load Cool Down Time
Uint32
Minute
N/A
RW
0 - 60
43568
EPS Current Threshold
Int32
PercentCTPri N/A
RW
3 - 10
43570
Fuel Level Function
Uint32
N/A
N/A
RW
0 = Disable
1 = Fuel Lvl
2 = Natural Gas
3 = Propane
43572
Number Flywheel Teeth
Uint32
N/A
N/A
RW
50 - 500