K
Max Input Voltage: Adjustable from 0 to 10 V in 1 V increments.
L
Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.
M
Threshold: –9999.0 to +9999.0 in increments of 0.1.
N
Activation Delay: Adjustable from 0 to 300 s in 1 s increments.
Remote RTD Inputs
An optional AEM-2020 (Analog Expansion Module) provides eight RTD inputs. To make identifying the
RTD inputs easier, a user-assigned name
A
can be given to each input.
Select the amount of hysteresis
B
and RTD type
C
. A user-adjustable arming delay
D
disables RTD input
recognition during engine startup. When enabled, an out of range alarm
E
alerts the user of an open or
damaged RTD input wire.
Each RTD input can be independently configured to annunciate an alarm, pre-alarm, or status only
F
when
the RTD input signal falls beyond the threshold
G
. A user-adjustable activation delay
H
setting delays alarm
annunciation after the threshold has been exceeded.
A remote RTD input is disabled when Alarm Configuration is set to “None”. Remote RTD input status is
available in BESTlogic+ Programmable Logic when “Status Only” is selected.
BESTCOMSPlus settings for remote RTD inputs (DGC-2020, Programmable Inputs, Remote RTD Inputs)
are illustrated in Figure 4-31. Remote RTD Input #1 is shown.
Figure 4-31. Remote RTD Inputs Settings
A
Label Text: An alphanumeric character string with a maximum of 16 characters.
B
Hysteresis: Adjustable from 0 to 100 percent in increments of 0.1%.
C
RTD Type: 100 Ohm Platinum or 10 Ohm Copper.
D
Arming Delay: Adjustable from 0 to 300 s in 1 s increments.
E
Out of Range Alarm Type: None, Alarm, Pre-Alarm, or Status Only.
F
Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.
G
Threshold: –58 to +482
F in 1F increments or –50 to +250C in 1C increments.
H
Activation Delay: Adjustable from 0 to 300 s in 1 s increments.
9400200990 Rev K
DGC-2020 BESTCOMSPlus Software