Name Description
Symbol
Hi Coolant Temp
TRUE when the High Coolant Temp Pre-Alarm
threshold has been exceeded.
High Fuel Level
TRUE when the High Fuel Level Pre-Alarm settings
have been exceeded.
Intergenset Comm
Fail
TRUE when an individual generator detects that it
had been connected to a generator network, but has
lost the connection.
Load Share Module
Load Share Module
Comm Fail
TRUE when communication from the LSM-2020 to
the DGC-2020 has been lost.
Load Share Module
Multiple Load Share
Modules Detected
TRUE when more than one LSM-2020 is connected.
Low Battery Voltage TRUE when the Low Battery Voltage Pre-Alarm
settings have been exceeded.
Low Coolant Level
TRUE when the Low Coolant Level function is
configured as a Pre-Alarm and the activation delay
has expired. In addition, TRUE when CANbus is
enabled and the Low Coolant Level Pre-Alarm
threshold has been exceeded.
Low Coolant Temp
TRUE when the Low Coolant Temp Pre-Alarm
threshold has been exceeded.
Low Fuel Level
TRUE when the Low Fuel Level Pre-Alarm threshold
has been exceeded.
Low
Oil
Pressure
TRUE when the Low Oil Pressure Pre-Alarm
threshold has been exceeded.
Maintenance
Interval
TRUE when the Maintenance Interval Pre-Alarm
threshold has been exceeded.
MPU Fail
TRUE when the MPU has failed.
Network ID Missing
Error
TRUE if an expected sequence ID of an optional
LSM-2020 is not detected on the network. Expected
sequence IDs are entered on the Network
Configuration screen.
Network ID Repeat
Error
TRUE if two or more optional LSM-2020’s report the
same expected sequence ID. Expected sequence
IDs are entered on the Network Configuration
screen.
Oil Pressure
Sender Fail
TRUE when the Oil Pressure Sender Fail is
configured as a Pre-Alarm and the activation delay
has expired.
Voltage Sensing
Fail
TRUE when the Voltage Sensing Fail is configured
as a Pre-Alarm and the activation delay has expired.
Weak Battery
TRUE when the Weak Battery Voltage Pre-Alarm
settings have been exceeded.
9400200990 Rev K
DGC-2020 BESTlogic+ Programmable Logic
5-9