Winco DGC-2020 User Manual
Page 62

3-14
DGC-2020 Functional Description
9400200990 Rev K
Event String
Event Description
Event
Type
ATS INPUT CLOSED
ATS Input
Status
AUTO RESTART
Automatic Restart in Progress
Status
AUTO RESTART FAIL A
Automatic Restart Fail
Alarm
BATT CHRG FAIL A
Battery Charger Fail
Alarm
BATT CHRG FAIL P
Battery Charger Fail
Pre-Alarm
BATT OVERVOLT P
Battery Overvoltage
Pre-Alarm
BATTLE OVERRIDE
Battle Override
Status
CEM COMM FAIL P
CEM-2020 Communications Failure
Pre-Alarm
CEM HW MISMATCH P
Connected CEM-2020 is wrong type
Pre-Alarm
CHECKSUM FAIL P
Corrupt user settings or firmware code
Pre-Alarm
COMBINED RED A
Combined Red
Alarm
COMBINED YELLOW P
Combined Yellow
Pre-Alarm
CONF PROT X (X = 1 to 8)
Configurable Protection X (X = 1 to 8)
Status
CONF PROT X A (X = 1 to 8)
Configurable Protection X (X = 1 to 8)
Alarm
CONF PROT X P (X = 1 to 8)
Configurable Protection X (X = 1 to 8)
Pre-Alarm
CONFIG ELEMENT X A (X = 1 to
8)
Configurable Element X (X = 1 to 8)
Alarm
CONFIG ELEMENT X P (X = 1 to
8)
Configurable Element X (X = 1 to 8)
Pre-Alarm
COOL LVL SNDR FL A
Coolant Level Sender Fail
Alarm
COOL SNDR FAIL
Coolant Temperature Sender Fail
Status
COOL SNDR FAIL A
Coolant Temperature Sender Fail
Alarm
COOL SNDR FAIL P
Coolant Temperature Sender Fail
Pre-Alarm
DEMAND START
Demand Start Request
Status
DEMAND STOP
Demand Stop Request
Status
DGC HEARTBEAT FAIL P
DGC Heartbeat Fail
Pre-Alarm
DIAG TRBL CODE P
Diagnostic Trouble Code
Pre-Alarm
DIAL OUT FAILED
Modem Dialout Failed
Status
DIAL OUT SUCCESS
Modem Dialout Success
Status
ECU SHUTDOWN A
ECU Shutdown
Alarm
EMERGENCY STOP A
Emergency Stop
Alarm
ENG KW OVRLD-1 P
Engine KW Overload 1
Pre-Alarm
ENG KW OVRLD-2 P
Engine KW Overload 2
Pre-Alarm
ENG KW OVRLD-3 P
Engine KW Overload 3
Pre-Alarm
ENGINE RUNNING
Engine Running
Status
FUEL LEAK 1 P
Fuel Filter 1 Leak
Pre-Alarm
FUEL LEAK 2 P
Fuel Filter 2 Leak
Pre-Alarm
FUEL LEAK DETECT A
Fuel Leak Detect
Alarm
FUEL LEAK DETECT P
Fuel Leak Detect
Pre-Alarm
FUEL LEVL SENDR FAIL
Fuel Level Sender Fail
Status
FUEL LEVL SENDR A
Fuel Level Sender Fail
Alarm
FUEL LEVL SENDR P
Fuel Level Sender Fail
Pre-Alarm
GEN TEST LOADED
Generator Exerciser Test with Load
Status
GEN TEST UNLOADED
Generator Exerciser Test without Load
Status
GLBL SNDR FAIL A
Global Sender Fail
Alarm
GN BKR CL FL P
Generator Breaker Fail to Close
Pre-Alarm