Alarms, High coolant temp alarm enable, High coolant temp alarm threshold – Winco DGC-2020 User Manual
Page 309: Metric high coolant temp alarm threshold, High coolant temp alarm activation delay, Low oil press. alarm enable, Low oil press. alarm threshold, Metric low oil press. alarm threshold, Low oil press. alarm arming delay

9400200990 Rev K
DGC-2020 Modbus
Communication
B-33
Register Description Type
Units
Scaling
Factor
R/W Range
44396
3 Phase Reverse Power Alarm
Configuration
Uint32 N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
44398
3 Phase Reverse Power
Hysteresis
Int32
DeciPercent Deci
RW
10 - 100
44400
1 Phase Reverse Power Pickup
Uint32 DeciPercent Deci
RW (-500)
-
50
44402
1 Phase Reverse Power
Activation Delay
Uint32 Decisecond
Deci
RW
0 - 300
44404
1 Phase Reverse Power Alarm
Configuration
Uint32 N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
44406
1 Phase Reverse Power
Hysteresis
Int32
DeciPercent Deci
RW
10 - 100
44408
3 Phase Loss of Excitation
Pickup
Uint32 DeciPercent Deci
RW (-1500)
-
0
44410
3 Phase Loss of Excitation
Activation Delay
Uint32 Decisecond
Deci
RW
0 - 300
44412
3 Phase Loss of Excitation
Alarm Configuration
Uint32 N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
44414
3 Phase Loss of Excitation
Hysteresis
Int32
DeciPercent Deci
RW
10 - 100
44416
1 Phase Loss of Excitation
Pickup
Uint32 DeciPercent Deci
RW (-1500)
-
0
44418
1 Phase Loss of Excitation
Activation Delay
Uint32 Decisecond
Deci
RW
0 - 300
44420
1 Phase Loss of Excitation
Alarm Configuration
Uint32 N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
44422
1 Phase Loss of Excitation
Hysteresis
Int32
DeciPercent Deci
RW
10 - 100
44424
3 Phase Overcurrent Reset
Type (51-1)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44426
1 Phase Overcurrent Reset
Type (51-1)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44428
3 Phase Overcurrent Reset
Type (51-2)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44430
1 Phase Overcurrent Reset
Type (51-2)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44432-498 FUTURE
USE
Alarms
Register Description Type
Units
Scaling
Factor
R/W
Range
44500
High Coolant Temp Alarm
Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44502
High Coolant Temp Alarm
Threshold
Uint32 Deg F
N/A
RW
100 - 280
44504
Metric High Coolant Temp Alarm
Threshold
Int32
Deg C
N/A
RW
38 - 138
44506
High Coolant Temp Alarm
Activation Delay
Uint32 Second
N/A
RW
0 - 150
44508
Low Oil Press. Alarm Enable
Uint32 N/A
N/A
RW
0 = Disable
1 = Enable
44510
Low Oil Press. Alarm Threshold
Uint32 PSI
N/A
RW
3 - 150
44512
Metric Low Oil Press. Alarm
Threshold
Int32
Kpa
N/A
RW
21 - 1034
44514
Low Oil Press. Alarm Arming
Delay
Uint32 Second
N/A
RW
5 - 15