Winco DGC-2020 User Manual
Page 286

B-10 DGC-2020
Modbus
Communication
9400200990 Rev K
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40049 Threshold
3-100
R
W
PSI
LOW BATTERY VOLTAGE PRE-ALARM
40050 Enable
0-1
R
W
0 =Off
1 =On
40051 Threshold
60-120 (12V)
120-240 (24V)
R W
.1 Volts DC
40052
Pre-alarm Activation Time Delay
1-10
R W
Seconds
WEAK BATTERY VOLTAGE PRE-ALARM
40053 Enable
0-1
R
W
0 =Off
1 =On
40054 Threshold
40-80 (12V)
80-160 (24V)
R W
.1 VoltDC
40055
Pre-alarm Activation Time Delay
1-10
R W
Seconds
40056-59 RESERVED
HIGH COOLANT TEMP ALARM
40060 Enable
0-1
R
W
0 =Off
1 =On
40061
Threshold
100-280
R W
Degrees F
40062
Arming Delay after Crank
Disconnect
60 R
W
Seconds
LOW OIL PRESSURE ALARM
40063 Enable
0-1
R
W
0 =Off
1 =On
40064 Threshold
3-100
R
W
PSI
40065
Arming Delay after Crank
Disconnect
5-15 R
W
Seconds
OVERSPEED ALARM
40066 Enable
0-1
R
W
0 =Off
1 =On
40067
Threshold
105-140
R W
% of Rated
40068
Alarm Activation Time Delay
0-500
R W
MilliSec
40069-71 RESERVED
CRANKING PARAMETERES
40072
Cranking Style
0-1
R W
0=Contin.
1=Cycle
40073
Number of Crank Cycles
1-7
R W
40074
Cycle Crank Time
5-15
R W
Seconds
40075
Continuous Crank Time
1-60
R W
Seconds
40076
Crank Disconnect Limit
10-100
R W
% of Rated
40077
Pre-crank Delay
0-30
R W
Seconds
SYSTEM MONITOR
40078
Remaining Cooldown Time
0-60
R
Minutes
40079 RESERVED
40080
Active Speed Signal Sources
1-4
R
1=MPU
2=ALT
3=GEN
4=NONE
40081
Sender Failure Alarm Code
individual bits
are 0 or 1
R
b0=High Coolant Temperature
b1=Oil Pressure
b2 Fuel Level
b3=Generator Voltage Sensing
b4=Magnetic Pick-up
b5-b7 not used