Table 3-4. event list -13 – Winco DGC-2020 User Manual
Page 61

9400200990 Rev K
DGC-2020 Functional Description
3-13
Table 3-4. Event List
Event String
Event Description
Event
Type
27-1 UNDVOLT TRP A
27-1 Undervoltage Trip
Alarm
27-1 UNDVOLT TRP P
27-1 Undervoltage Trip
Pre-Alarm
27-2 UNDVOLT TRP A
27-2 Undervoltage Trip
Alarm
27-2 UNDVOLT TRP P
27-2 Undervoltage Trip
Pre-Alarm
32 RVS PWR TRP A
32 Reverse Power Trip
Alarm
32 RVS PWR TRP P
32 Reverse Power Trip
Pre-Alarm
40 EXC LOSS TRP A
40 Loss of Excitation Trip
Alarm
40 EXC LOSS TRP P
40 Loss of Excitation Trip
Pre-Alarm
47 PHS IMBAL TRP A
47 Phase Imbalance Trip
Alarm
47 PHS IMBAL TRP P
47 Phase Imbalance Trip
Pre-Alarm
51-1 OVRCURR TRP A
51-1 Overcurrent Trip
Alarm
51-1 OVRCURR TRP P
51-1 Overcurrent Trip
Pre-Alarm
51-2 OVRCURR TRP A
51-2 Overcurrent Trip
Alarm
51-2 OVRCURR TRP P
51-2 Overcurrent Trip
Pre-Alarm
59-1 OVRVOLT TRP A
59-1 Overvoltage Trip
Alarm
59-1 OVRVOLT TRP P
59-1 Overvoltage Trip
Pre-Alarm
59-2 OVRVOLT TRP A
59-2 Overvoltage Trip
Alarm
59-2 OVRVOLT TRP P
59-2 Overvoltage Trip
Pre-Alarm
81O OVRFREQ TRP A
81 Overfrequency Trip
Alarm
81O OVRFREQ TRP P
81 Overfrequency Trip
Pre-Alarm
81U UNDFREQ TRP A
81 Underfrequency Trip
Alarm
81U UNDFREQ TRP P
81 Underfrequency Trip
Pre-Alarm
AEM COMM FAIL P
AEM-2020 Communications Failure
Pre-Alarm
AEM OUTX OUT RNG (X = 1 to 4)
User Configurable Analog Output X Out of Range (X = 1 to 4)
Status
AEM OUTX OUT RNG A (X = 1 to
4)
User Configurable Analog Output X Out of Range (X = 1 to 4)
Alarm
AEM OUTX OUT RNG P (X = 1 to
4)
User Configurable Analog Output X Out of Range (X = 1 to 4)
Pre-Alarm
AL ECU FAULTY P
ECU Faulty
Pre-Alarm
ALG IN X_O1 (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Status
ALG IN X_O1 A (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Alarm
ALG IN X_O1 P (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Pre-Alarm
ALG IN X_O2 (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Status
ALG IN X_O2 A (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Alarm
ALG IN X_O2 P (X = 1 to 8)
User Configurable Analog Input X Over 1 (X = 1 to 8)
Pre-Alarm
ALG IN X_OOR (X = 1 to 8)
User Configurable Analog Input X Out of Range (X = 1 to 8)
Status
ALG IN X_OOR A (X = 1 to 8)
User Configurable Analog Input X Out of Range (X = 1 to 8)
Alarm
ALG IN X_OOR P (X = 1 to 8)
User Configurable Analog Input X Out of Range (X = 1 to 8)
Pre-Alarm
ALG IN X_U1 (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Status
ALG IN X_U1 A (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Alarm
ALG IN X_U1 P (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Pre-Alarm
ALG IN X_U2 (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Status
ALG IN X_U2 A (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Alarm
ALG IN X_U2 P (X = 1 to 8)
User Configurable Analog Input X Under 1 (X = 1 to 8)
Pre-Alarm
ALT WIRE TMP HI P
Alternator Wiring Temp High
Pre-Alarm