Winco DGC-2020 User Manual
Page 167

Name Description
Symbol
Status Input
Load Share Module
Load Share Module Connected. TRUE when an
optional LSM-2020 is connected to the DGC-2020.
Status Input
Load Share Module
Load Share Module Governor Output Limit. TRUE
when the LSM-2020 Governor Output Limit settings
have been exceeded.
Status Input
Low Line Override
TRUE when the Low Line Override input is TRUE.
Status Input
Off Mode
TRUE when the DGC-2020 is in Off Mode.
Status Input
PF Mode Active
TRUE when PF mode is active.
Status Input
Pre Start Condition
in Effect
TRUE while in the Pre Start state.
Status Input
Pre Start Input
TRUE when the DGC-2020 is indicating that the Pre
Start relay should be closed.
Status Input
Reset Active
TRUE while the Reset button on the HMI is pressed.
Status Input
Run Input
TRUE when the DGC-2020 is indicating that the
Run Input should be closed.
Status Input
Run Mode
TRUE when the DGC-2020 is in Run Mode.
Status Input
Single Phase AC
Sensing Override
TRUE when the Single Phase AC Override input is
TRUE.
Status Input
Single Phase
Connection
Override
TRUE when the Single Phase Override input is
TRUE.
Status Input
Switch not in Auto
TRUE when the DGC-2020 is not in Auto Mode.
Status Input
Start Input
TRUE when the DGC-2020 is indicating that the
Start relay should be closed to start the engine.
Status Input
VAR Mode Active
TRUE when Var mode is active.
Output Objects
Physical Outputs
OUT1 - OUTx
Physical Outputs 1 through 7 (style xxAxxxxx) or 1
through 15 (style xxBxxxxx).
Remote Outputs
OUT13 - OUT36
Remote Outputs 13 through 36.
(Available when an optional CEM-2020 is
connected.)