beautypg.com

Winco DGC-2020 User Manual

Page 168

background image

Name Description

Symbol

Alarms

Analog Expansion
Module

Remote Analog
Inputs 1-8

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)

Analog Expansion
Module

Remote Analog
Outputs 1-4

TRUE when the analog output connection is open
and the Out of Range Alarm Configuration is set to
Alarm.

Analog Expansion
Module

Remote RTD Inputs
1-8

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)

Analog Expansion
Module

Remote
Thermocouple
Inputs 1-2

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)

Auto Restart Fail

TRUE after the Automatic Restart function fails to
restart the generator.

Battery Charger Fail TRUE when the Battery Charger Fail function is

configured as an Alarm and the activation delay has
expired.

Configurable
Protection

Protection 1-8

TRUE when Over 1, Over 2, Under 1, or Under 2 is
configured as an Alarm and the threshold has been
exceeded. (Over 1 shown.)

Coolant Level
Sender Fail

TRUE when a low coolant level error status code is
received from the ECU. CANbus must be enabled.

Coolant Temp
Sender Fail

TRUE when the Coolant Temp Sender Fail is
configured as an Alarm and the activation delay has
expired.

ECU Comm Loss

TRUE when communication to ECU has been lost.

ECU Shutdown

TRUE when ECU has Shutdown the engine.

Emergency Stop

TRUE when the Emergency Stop button has been
pressed.

Fuel

Leak

TRUE when the Fuel Leak Detect function is
configured as an Alarm and the activation delay has
expired.

Fuel Level Sender
Fail

TRUE when the Fuel Level Sender Fail is
configured as an Alarm and the activation delay has
expired.

Global Alarm

TRUE when one or more Alarms are set.

Global Sender Fail

TRUE when one or more of the Sender Fails are
configured as Alarms and are TRUE.

5-6

DGC-2020 BESTlogic+ Programmable Logic

9400200990 Rev K