Winco DGC-2020 User Manual
Page 168

Name Description
Symbol
Alarms
Analog Expansion
Module
Remote Analog
Inputs 1-8
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)
Analog Expansion
Module
Remote Analog
Outputs 1-4
TRUE when the analog output connection is open
and the Out of Range Alarm Configuration is set to
Alarm.
Analog Expansion
Module
Remote RTD Inputs
1-8
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)
Analog Expansion
Module
Remote
Thermocouple
Inputs 1-2
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as an Alarm and the
threshold has been exceeded. (Over 1 shown.)
Auto Restart Fail
TRUE after the Automatic Restart function fails to
restart the generator.
Battery Charger Fail TRUE when the Battery Charger Fail function is
configured as an Alarm and the activation delay has
expired.
Configurable
Protection
Protection 1-8
TRUE when Over 1, Over 2, Under 1, or Under 2 is
configured as an Alarm and the threshold has been
exceeded. (Over 1 shown.)
Coolant Level
Sender Fail
TRUE when a low coolant level error status code is
received from the ECU. CANbus must be enabled.
Coolant Temp
Sender Fail
TRUE when the Coolant Temp Sender Fail is
configured as an Alarm and the activation delay has
expired.
ECU Comm Loss
TRUE when communication to ECU has been lost.
ECU Shutdown
TRUE when ECU has Shutdown the engine.
Emergency Stop
TRUE when the Emergency Stop button has been
pressed.
Fuel
Leak
TRUE when the Fuel Leak Detect function is
configured as an Alarm and the activation delay has
expired.
Fuel Level Sender
Fail
TRUE when the Fuel Level Sender Fail is
configured as an Alarm and the activation delay has
expired.
Global Alarm
TRUE when one or more Alarms are set.
Global Sender Fail
TRUE when one or more of the Sender Fails are
configured as Alarms and are TRUE.
5-6
DGC-2020 BESTlogic+ Programmable Logic
9400200990 Rev K