Bestlogic+ composition, Bestlogic+ composition -2, I/o -2 – Winco DGC-2020 User Manual
Page 164: Table 5-1. i/o group, names and descriptions -2

BESTlogic+ Composition
There are three main groups of objects used for programming BESTlogic+. These groups are I/O,
Components, and Elements. For details on how these objects are used to program BESTlogic+, see the
paragraphs on Programming BESTlogic+.
I/O
This group contains Input Objects, Output Objects, Alarms, Pre-Alarms, and Senders. Table 5-1 lists the
names and descriptions of the objects in the I/O group.
Table 5-1. I/O Group, Names and Descriptions
Name Description
Symbol
Input Objects
Logic 0
Always FALSE (Low).
Logic 1
Always TRUE (High).
Physical Inputs
IN1 - IN16
TRUE when Physical Input x is active.
Remote Inputs
IN17 - IN26
True when Remote Input x is active.
(Available when an optional CEM-2020 is
connected.)
Virtual Inputs
VIN1 - VIN4
TRUE when Virtual Input x is active.
Status Input
Analog Expansion
Module
Analog Expansion Module Connected. TRUE when
an optional AEM-2020 is connected to the DGC-
2020.
Analog Expansion
Module
Remote Analog
Inputs 1-8
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)
Analog Expansion
Module
Remote Analog
Outputs 1-4
TRUE when the analog output connection is open
and the Out of Range Alarm Configuration is set to
Status Only.
Analog Expansion
Module
Remote RTD Inputs
1-8
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)
Analog Expansion
Module
Remote
Thermocouple
Inputs 1-2
TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)
Status Input
ATS Input
TRUE when the ATS (Auto Transfer Switch) input is
TRUE.
Status Input
Audible Horn
TRUE when the Audible Horn is active.
Status Input
Auto Mode
TRUE when the DGC-2020 is in Auto Mode.
5-2
DGC-2020 BESTlogic+ Programmable Logic
9400200990 Rev K